View larger
PKE65/XTU-65 138516 Y7-138516 EATON ELECTRIC Motor-protective circuit-breaker, 3p, +control option 8-65A
PKE65/XTU-65
138516
Y7-138516
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKE65/XTU-65 is a motor-protective circuit-breaker engineered to safeguard industrial electrical circuits and rotating machinery from overcurrent conditions. Such devices are typically deployed within distribution boards and motor control centers to provide reliable disconnection and protection against electrical faults during abnormal operating scenarios. Pricing, availability, and lead times are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 16 A
- Adjustment range undelayed short-circuit release (EF007131): 1008 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 65 A
- Rated operation power at AC-3, 230 V (EF007025): 18.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 30 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
CSA-C22.2 No. 60947-4-1-14
CSA
UL Category Control No.: NLRV
UL File No.: E36332
CSA File No.: 165628
UL
UL 60947-4-1
VDE 0660
IEC/EN 60947
CSA Class No.: 3211-05
IEC/EN 60947-4-1
Features & Functions
Overload release
Motor protection
General
900 (Class 15) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
700 (Class 10) AC-4 cycle operation, Main conducting paths
500 (Class 5) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
Terminals: IP00
-25 - 55 °C, Operating range
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (0.75 - 35) mm², ferrule to DIN 46228
2 x (0.75 - 16) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
200 A, Class J, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
± 20% tolerance, Trip blocks
Delayed approx. 60 ms, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks
Switching capacity
58 A, General use UL/CSA