EATON - MOELLER Z-MS-2,5/2 Z-MS-2,5/2 248395 Y7-248395 EATON ELECTRIC Motor-Protective Circuit-Breakers, 1, 6-2, 5 A, 2 p View larger
Images are for illustrative purposes only. Please refer to data sheet for details

Z-MS-2,5/2 248395 Y7-248395 EATON ELECTRIC Motor-Protective Circuit-Breakers, 1, 6-2, 5 A, 2 p

Z-MS-2,5/2

248395

Y7-248395

EATON - MOELLER

1 Pcs.

Motor-Protective Circuit-Breakers, 1, 6-2, 5 A, 2 p Z-MS-2,5/2 Motor-protective circuit-breaker with thermal overload release and magnetic short-circuit release, for switching and protecting three-phase motors with outputs of up to 15 kW (380/400 V) or other loads with currents of up to 40 A, can also be used as a main switch, isolating characteristics to IEC/EN 60947, contact position display red/green

Automation > Motor protection circuit-breaker
Modular Switchgear – Others and Accessories

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Manufactured by Eaton Moeller, the Z-MS-2,5/2 motor-protective circuit-breaker delivers specialized two-pole protection for electrical equipment against thermal and magnetic anomalies. Control engineers install these devices to protect smaller drives from unexpected overcurrent conditions and phase irregularities. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Overload release current setting (EF002336): 1.6 A
  • Adjustment range undelayed short-circuit release (EF007131): 25 A
  • With thermal overload protection (EF006233): Yes
  • Phase failure sensitive (EF007400): No
  • Switch off technique (EF007007): Magnetic
  • Rated operating voltage (EF001435): 400 V
  • Rated permanent current Iu (EF001389): 2.5 A
  • Rated operation power at AC-3, 230 V (EF007025): 0 kW
  • Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
  • Type of electrical connection of main circuit (EF006819): Screw connection
  • Type of control element (EF006976): Rocker lever
  • Device construction (EF008240): Complete device in housing
  • With integrated auxiliary switch (EF001387): No
  • With integrated under voltage release (EF001390): No
  • Number of poles (EF001391): 2
  • Degree of protection (IP) (EF005474): IP20

More info

▲
Motor-Protective Circuit-Breakers, 1,6-2,5A, 2p
Motor-protective circuit-breaker with thermal overload release and magnetic short-circuit release, for switching and protecting three-phase motors with outputs of up to 15 kW (380/400 V) or other loads with currents of up to 40 A, can also be used as a main switch, isolating characteristics to IEC/EN 60947, contact position display red/green

General specifications
Product name
Eaton Distribution parts
Part no.
Z-MS-2,5/2
EAN
4015082483951
Product Length/Depth
80 millimetre
Product height
75 millimetre
Product width
36 millimetre
Product weight
0.244 kilogram
Compliances
RoHS conform
Product Tradename
None
Product Type
Distribution parts
Product Sub Type
None
Public Consumption
Yes
Product Family Description
ES-PMCC-PDC-Eaton Distribution parts
Globally Marketable
Yes
Product Specification Details
Actuator type
Rocker lever
Adjustment range short-term delayed short-circuit release - min
25 A
Adjustment range undelayed short-circuit release - max
33 A
Adjustment range undelayed short-circuit release - min
25 A
Degree of protection
IP20
Device construction
Complete device in housing
Electrical connection type of main circuit
Screw connection
Equipment heat dissipation, current-dependent
3.7 W
Fitted with:
Thermal protection
Heat dissipation per pole, current-dependent
1.85 W
Number of poles
Two-pole
Overload release current setting - max
2.5 A
Overload release current setting - min
1.6 A
Rated operating power at AC-3, 230 V
0 kW
Rated operating power at AC-3, 400 V
0.75 kW
Rated operating voltage (Ue) - max
400 V
Rated operating voltage (Ue) - min
400 V
Rated operational current for specified heat dissipation (In)
2.5 A
Rated short-circuit breaking capacity at 400 V AC
10 kA
Rated uninterrupted current (Iu)
2.5 A
Switch off technique
Magnetic

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss13-27-37-04-01 [AGZ529021])
Overload release current setting
1.6 - 2.5 A
Adjustment range undelayed short-circuit release
25 - 33 A
With thermal overload protection
Yes
Phase failure sensitive
No
Switch off technique
Magnetic
Rated operating voltage
400 - 400 V
Rated permanent current Iu
2.5 A
Rated operation power at AC-3, 230 V
0 kW
Rated operation power at AC-3, 400 V
0.75 kW
Power loss
W
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
Device construction
Complete device in housing
With integrated auxiliary switch
No
With integrated under voltage release
No
Number of poles
2
Rated short-circuit breaking capacity lcu at 400 V, AC
10 kA
Degree of protection (IP)
IP20
Height
75 mm
Width
36 mm
Depth
80 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.