Images are for illustrative purposes only. Please refer to data sheet for details
MCCB2-200/I43E-200 138541 Y7-138541 EATON ELECTRIC Housing, insulated material, for molded-case circuit-brea..
MCCB2-200/I43E-200
138541
Y7-138541
EATON - MOELLER
1 Pcs.
Housing, insulated material, for molded-case circuit-breaker NZM2 size, HxWxD=375x250x225mm
MCCB2-200/I43E-200
Eaton xEnergy Safety Ci LV systems LV switchgear. Housing, insulated material, for molded-case circuit-breaker NZM2 size, HxWxD=375x250x225mm
Enclosure for molded-case circuit-breaker and switch-disconnector, material characteristic polycarbonate, impact-resistant, degree of protection IP65, patented cover fasteners with integrated overpressure compensation, use as individual enclosure and distribution board, observe the technical data of other equipment when connecting distribution boards, metric cable entry knockouts in all sides, enclosure side plates can be knocked out or grouped next to other devices, mounting plate pre-drilled for switch and pre-drilled for a PE and N terminal, mounting plate made from 3mm sheet steel, sealable cover fasteners, cover type: transparent smoky , predrilled, degree of protection IP65, with switch door coupling rotary handle NZM...-XTVD and extension shaft, fixing material for fixing material, fixing strap BL-CI, not in combination with remote operator NZM…-XR, plug-in unit NZM…-XSV or withdrawable unit NZM…-XAV, rated uninterrupted current Iu=200 A, can be used for switch NZM2(-4), N2(-4), N(N/O)2(-4), can be used for terminals K50/1, K95/1N…, K150/1N…, notes: additional terminals for PE- and N-conductor K50/1 K95/1N..., K150/1N... for 4. and 5. pole must be ordered separately
Automation > Empty enclosure for switchgear Insulating Enclosures
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
N2(-4) NZM2(-4) LZM2(-4) PN2(-4) LN2(-4) K150/1N… K95/1N… K50/1 NS2 Enclosures for circuit breakers, switch-disconnectors Prepared enclosures xEnergy Safety Ci
Special features
For use as individual enclosures (order insulated additional terminal for 4th or 5th pole separately) or in distribution boardsObserve the technical data of other equipment when connecting distribution boardsMetric cable entry knockouts in all sidesSide walls can be knocked out or fitted next to other devicesGalvanized sheet steel mounting plate pre-drilled for switches & PE and N terminalSealable cover fastenersWith door coupling rotary handle NZM…-XTVD and extension shaftFixing material for fixing materialIncluding fixing straps for wall mountingcan not be combined with remote operator NZM...-XR, plug-in unit NZM...-XSV or withdrawable unit NZM...-XAV
Type
Enclosures for circuit breakers, switch-disconnectorsPrepared enclosuresxEnergy Safety Ci
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
Fitted with:
Transparent cover
Enclosure
CI43E-200
Degree of protection
IP65 Other
Enclosure material
Plastic
Unit type
Complete housing
Voltage rating
690 V AC
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
28 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
22 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
25 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
55 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
45 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
50 W
Cover/door type
Transparent, smoke gray, pre-drilled for door coupling rotary handle
Functions
Prepared enclosure
Model
Surface mounting
Rated uninterrupted current (Iu)
200 A
Voltage rating at AC
690 V AC
Suitable for
Emergency stop
ETIM for 138541 Low-voltage industrial controls and switchgear (EC000712)
Feature Name
Feature Value
Housing material (EF001596)
Plastic
Width (EF000008)
375 mm
Height (EF000040)
250 mm
Depth (EF000049)
225 mm
With transparent cover (EF001094)
Yes
Suitable for emergency stop (EF001433)
Yes
Model (EF000010)
Surface mounting
Degree of protection (IP) (EF005474)
IP65
Degree of protection (NEMA) (EF011959)
Other
Product Datasheet
Electrica Online Product DatasheetPrepared from the current product description, catalog data and structured technical attributes.