EATON - MOELLER AE/I44E/T AE/I44E/T 061937 Y7-61937 EATON ELECTRIC MCB enclosure, +door, 3x15space units, HxWxD 375x375x150mm View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AE/I44E/T 061937 Y7-61937 EATON ELECTRIC MCB enclosure, +door, 3x15space units, HxWxD 375x375x150mm

AE/I44E/T

061937

Y7-61937

EATON - MOELLER

1 Pcs.

MCB enclosure, +door, 3x15space units, HxWxD=375x375x150mm Eaton xEnergy Safety Ci LV systems LV switchgear. MCB enclosure, +door, 3x15space units, HxWxD=375x375x150mm MCB individual enclosure with door, material characteristic polycarbonate, impact-resistant, degree of protection IP65, metric cable entry knockouts in all sides, for mounting devices with frame size 1 to DIN 43880, transparent smoky cover with quick-release fasteners, transparent smoky door for operator access to devices fitted, mounting rails for snap-fitting the devices, blanking strip for unused mounting locations, protective shroud with inscription label, including space unit/N bars, fixing straps for wall fixing, sealable cover fasteners, number space units=45 , space unit and N-terminals count x cross-section=each 4x(6-35)mm² and 20x(1-4)mm², cover type: transparent smoky, door type: transparent smoky

Automation > Small distribution board
Insulating Enclosures

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton xEnergy Safety Ci MCB enclosure
Catalog Number
061937
Model Code
AE/I44E/T
EAN
4015080619376
Product Length/Depth
150 mm
Product Height
375 mm
Product Width
375 mm
Product Weight
3.88 kg
Compliances
RoHS conform
Certifications
EN 61439-2
EN 62208

Product specifications

Special features
Type
  • MCB individual enclosures
  • Prepared enclosure
  • xEnergy Safety Ci
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
20 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
Enclosure material
Plastic
Accessory/spare part type
MCB individual enclosures
Built-in height
0 mm
Built-in width
0 mm
Unit type
Stand-alone device
Built-in depth
100 mm
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
25 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
23 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
24 W
Closure type
Other
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Door
Transparent
Single
RAL-number
7035
Width in number of modular spacings
15
Color
Gray
Number of rows
3
Number of module space units (total)
45
Degree of protection
IP65
Number and capacity of terminal (PE and N)
On each 3 x (2.5 - 25 mm²)
On each 21 x (0.5 - 4 mm²)
Functions
Prepared enclosure
Mounting method
DIN-rail
Surface mounted (plaster)
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
51 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
45 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
48 W
Internal depth
150 mm

ETIM for 061937 Distribution boards (EC000214)
Feature Name Feature Value
Mounting method (EF000003) Surface mounted
Number of rows (EF000266) 3
Width in number of modular spacings (EF002950) 15
Type of covering (EF000339) Door
Cover model (EF009212) Closed
Type of door (EF004464) EV000426
Transparent cover/door (EF006244) Yes
Signal passing door (EF015941) No
With lock (EF006306) No
Type of closure (EF004462) Other
Housing material (EF001596) Plastic
Built-in depth (EF000218) 100 mm
Built-in height (EF000332) 0 mm
Built-in width (EF000846) 0 mm
Inner depth (EF001131) 150 mm
Earthing terminal block (EF015776) No
Neutral terminal block (EF015777) No
DIN-rail (EF001134) Yes
With mounting plate (EF000118) No
Extension possible (EF001088) No
EMC-version (EF001062) No
Colour (EF000007) Grey
RAL-number (EF000116) 7035
Degree of protection (IP) (EF005474) IP65
Height (EF000040) 375 mm
Width (EF000008) 375 mm
Depth (EF000049) 150 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.