An Eaton Moeller P1-32/V/SVB/HI11 main switch combines a 32A capacity with integrated emergency stop functionality and auxiliary contacts for comprehensive machine safety. These compact disconnectors are commonly mounted on control panel doors to provide direct power interruption capabilities.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 32 A
- Rated permanent current at AC-23, 400 V (EF011777): 32 A
- Rated permanent current at AC-21, 400 V (EF009165): 32 A
- Rated operation power at AC-3, 400 V (EF001364): 13 kW
- Rated short-time withstand current lcw (EF007050): 0.64 kA
- Rated operation power at AC-23, 400 V (EF007027): 15 kW
- Switching power at 400 V (EF009166): 15 kW
- Conditioned rated short-circuit current Iq (EF001444): 80 kA
More info
▲General specifications
UL File No.: E36332
IEC/EN 60204
VDE 0660
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-3
UL Category Control No.: NLRV
CSA
CE
CSA File No.: 012528
UL 60947-4-1
CSA Class No.: 3211-05
CSA-C22.2 No. 94
UL