View larger
P5-315/EA/SVB/HI10 280951 Y7-280951 EATON ELECTRIC Main switch, 3 pole + 1 N/O, 315 A, Emergency-Stop functi..
P5-315/EA/SVB/HI10
280951
Y7-280951
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Disconnectors and Cam Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Functioning as a heavy-duty main switch with emergency stop capabilities, this Eaton Moeller unit provides reliable disconnection and isolation of high-current power networks. Industrial facilities incorporate these safety-rated devices into primary distribution boards to protect operators and machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 315 A
- Rated permanent current at AC-23, 400 V (EF011777): 315 A
- Rated permanent current at AC-21, 400 V (EF009165): 315 A
- Rated operation power at AC-3, 400 V (EF001364): 75 kW
- Rated short-time withstand current lcw (EF007050): 5.8 kA
- Rated operation power at AC-23, 400 V (EF007027): 110 kW
- Switching power at 400 V (EF009166): 110 kW
- Conditioned rated short-circuit current Iq (EF001444): 15 kA
More info
▲General specifications
CSA Std. C22.2 No. 14-05
EN 60947-3
UL 508
VDE
CE
IEC/EN 60947
UL Category Control No.: NLRV, NLRV7
VDE 0660
IEC/EN 60947-3
UL File No.: E36332
CSA Class No.: 3211-05
CSA File No.: 223805
CSA-C22.2 No. 14-05
CSA
IEC/EN 60204
CSA-C22.2 No. 94
UL