Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
-5 - +40
Interval between busbar centres
100 mm
Number of poles/phases
3 n
Mounting position
Vertical, horizontal
Overvoltage category/pollution degree
III/3
Protection type
IP30 (Operating state)
IP10 (Front cover open)
Degree of Protection
IP30
Direction of incoming supply
as required
Lifespan, mechanical [Operations]
1400
Rated frequency [f]
50 - 60 Hz
Rated insulation voltage [Ui]
1000 V
Rated operating mode
continuous operation
Rated impulse withstand voltage [Uimp]
8 kV
Interval between busbar centres
100 mm
Overvoltage category/pollution degree
III/3
Rated operational current [Ie]
160 A
Rated conditional short-circuit current AC [Iq]
50 kAeff
Utilization category AC22BRated operating voltage [Ue]
690 V AC
Utilization category AC22BRated operating current [Ie]
160 A
Utilization category AC-23BRated operating voltage [Ue]
500/400 V AC
Utilization category AC-23BRated operating current [Ie]
125/160 A
Utilization category AC-21BRated operating voltage [Ue]
690 V AC
Utilization category AC-21BRated operating current [Ie]
160 A
Electrical
≧ 200 Operations
Heat dissipation at IthAC, without NH-SE
20 W
Rated operational voltage [Ue]Rated operating voltage [Ue]
400 V AC
Rated frequency [f]
50 - 60 Hz
Rated operational current [Ie]
160 A
Conventional thermal current [Ith]
160 A
Control mode
Uninterrupted operation
Rated impulse withstand voltage [Uimp]
8 kV
Power lossFuse
20 W at 160 A W
Electrical
≧ 200 Operations
Lifespan, mechanical [Operations]
1400
Max. rated operational current gL/gG
160 A
Max. admissible heat dissipation NH-SE [Pv]
12 W
Box terminalCopper band [Number of segments x width x thickness ]
6 x 9 x 0.8 mm
Flange connectionDiameter [d]
M8 mm
Flange connectionStranded with cable lug
1 x 70 mm2
Flange connectionFlat busbar [max.]
20 x 10 mm
Box terminalStranded
1.5 - 70 mm2
Box terminalFlat conductor [Lamellenzahl x Breite x Dicke ]
6 x 9 x 0.8 mm
Mounting on busbarsAdapter for busbars
Z-…SAD
Z-…SADD
Mounting on busbarsScrew connection for busbars
Only in combination with adapter for
M8
… x 5/10
Lifespan, mechanical [Operations]
1400
Overvoltage category/pollution degree
III/3