Request QuoteProduct Overview
Eaton Moeller PKZM0-XDM12 is a wiring set and component adapter kit used to build direct-on-line starter assemblies in industrial machinery. Modular wiring accessories eliminate loose control jumpers, providing clean mechanical and electrical connections between protection devices and contactors.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series PKZM0 Accessory Wiring set
- Catalog Number: 283149
- Model Code: PKZM0-XDM12
- EAN: 4015082831493
- Product Length/Depth: 91 mm
- Product Height: 67 mm
- Product Width: 45 mm
- Product Weight: 0.058 kg
- Catalog Notes: Cannot be combined with NHI‐E…PKZ0‐PI. Ue ≦ 415 V
- Model: Direct circuit
- Product category: Accessories
- Type: Wiring set
- Ambient operating temperature - min: -25 °C
- Ambient operating temperature - max: 55 °C
- Rated operational current (Ie): 15 A
More info
▲General specifications
| Product Name | Eaton Moeller® series PKZM0 Accessory Wiring set |
| Catalog Number | 283149 |
| Model Code | PKZM0-XDM12 |
| EAN | 4015082831493 |
| Product Length/Depth | 91 mm |
| Product Height | 67 mm |
| Product Width | 45 mm |
| Product Weight | 0.058 kg |
| Certifications | UL UL File No.: E36332 CSA-C22.2 No. 14 CE CSA IEC/EN 60947-4-1 CSA Class No.: 3211-05 CSA File No.: 165628 UL 508 UL Category Control No.: NLRV |
| Catalog Notes | Cannot be combined with NHI‐E…PKZ0‐PI. Ue ≦ 415 V |
General information
| Accessories | Cable routing, main current wiring between PKZM0 and contactor with tool-less plug connection, mechanical connection element for PKZM0 and contactor included with supplied equipment. |
| Model | Direct circuit |
| Product category | Accessories |
| Product category | Accessories |
| Type | Wiring set |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 55 °C |
Electrical rating
| Rated operational current (Ie) | 15 A |
| Rated operational voltage (Ue) - max | 415 VAC |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 1.5 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.5 W |
| Rated operational current for specified heat dissipation (In) | 15.5 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |