View larger
INX40B3-10W-1 184057 Y7-184057 EATON ELECTRIC Switch-disconnector, 3 pole, 1000 A, without protection, IEC, ..
INX40B3-10W-1
184057
Y7-184057
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers IZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for high-amperage electrical systems, this Eaton Moeller INX40B3-10W-1 switch-disconnector provides robust load-break switching and isolation capabilities for demanding industrial power networks. Heavy-duty switch-disconnectors are standard installations in main distribution boards where reliable manual disconnection of heavy electrical loads is required. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): No
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 1000 A
- Rated permanent current at AC-23, 400 V (EF011777): 1000 A
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 66 kA
- Rated operation power at AC-23, 400 V (EF007027): 0 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 144 kA
More info
▲General specifications
IEC/EN 60947
RoHS conform
Delivery program
Technical data - electrical
20000 operations (switching cycles ON/OFF, with maintenance)
Technical data - mechanical
IP31 with door seals
12500 switching cycles (ON/OFF)
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Motor drive optional
Version as main switch
Interlockable
- Cassette must be separately ordered.
- Optionally fittable by user with comprehensive accessories
- Terminal capacity hint: These are values used in separate switchgear. The actual values will depend on the temperature around the circuit breaker, which is influenced by the ambient temperature, the degree of protection (IP), the mounting height, the partitions, and any external ventilation. Depending on the specific switchgear design, this may result in derating, which can then be compensated for by increasing the cross-sectional area. Temperature rise tests in the specific switchgear can provide specific and detailed information.
Distribution board installation
Ground mounting
Open switch-disconnector