EATON - MOELLER CI-PKZ0-GRM CI-PKZ0-GRM 260104 Y7-260104 EATON ELECTRIC Insulated enclosure, IP55 x, rotary handle red yellow, for PKZ0 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CI-PKZ0-GRM 260104 Y7-260104 EATON ELECTRIC Insulated enclosure, IP55 x, rotary handle red yellow, for PKZ0

CI-PKZ0-GRM

260104

Y7-260104

EATON - MOELLER

1 Pcs.

Insulated enclosure, IP55_x, rotary handle red yellow, for PKZ0 CI-PKZ0-GRM Insulated enclosure for PKZM0, degree of protection IP55 integrated terminal for PE(N) connection., Per 2 M25 knockout cable entries, with red-yellow rotary handle

Automation > Empty enclosure for switchgear
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Insulated enclosure, IP55_x, rotary handle red yellow, for PKZ0
Insulated enclosure for PKZM0, degree of protection IP55 integrated terminal for PE(N) connection., Per 2 M25 knockout cable entries, with red-yellow rotary handle

General specifications
Product name
Eaton Moeller® series CI Insulated enclosure
Part no.
CI-PKZ0-GRM
EAN
4015082601041
Product Length/Depth
25 millimetre
Product height
160 millimetre
Product width
80 millimetre
Product weight
0.2 kilogram
Compliances
Contact Manufacturer
Certifications
CE
Product Tradename
CI
Product Type
Insulated enclosure
Product Sub Type
None
Features & Functions
Enclosure material
Plastic
Fitted with:
Red-yellow rotary knob, for use as EMERGENCY STOP switch (according to EN 60204)
PE(N) terminal
Knockouts
Hard mirror with cable entry knockouts (can be cut out)
2 x M25 (cable entry knockout with thread at the top)
2 x M25 (cable entry knockout with thread at the bottom)
2 x M20 (cable entry knockouts at the rear)
General information
Degree of protection
IP55
NEMA Other
Model
Surface mounting
Product category
Accessories
Suitable for
Emergency stop
Used with
PKZM0
+L-PKZ0 (2 units), +NHI or U or A, PKZM0-…
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
10 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Empty enclosure for switchgear (EC000712)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Empty housing for switch devices (ecl@ss13-27-37-13-01 [AKN343019])
Housing material
Plastic
Width
80 mm
Height
160 mm
Depth
25 mm
With transparent cover
No
Suitable for emergency stop
Yes
Model
Surface mounting
Degree of protection (IP)
IP55
Degree of protection (NEMA)
Other

ETIM for 260104 Low-voltage industrial controls and switchgear (EC000712)
Feature Name Feature Value
Housing material (EF001596) Plastic
Width (EF000008) 80 mm
Height (EF000040) 160 mm
Depth (EF000049) 25 mm
With transparent cover (EF001094) No
Suitable for emergency stop (EF001433) Yes
Model (EF000010) Surface mounting
Degree of protection (IP) (EF005474) IP55