EATON - MOELLER CI-K2H-T3-4 CI-K2H-T3-4 105859 Y7-105859 EATON ELECTRIC Insulated enclosure, for T3-4 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CI-K2H-T3-4 105859 Y7-105859 EATON ELECTRIC Insulated enclosure, for T3-4

CI-K2H-T3-4

105859

Y7-105859

EATON - MOELLER

1 Pcs.

Insulated enclosure, for T3-4 CI-K2H-T3-4 Eaton Moeller® series CI-K Insulated enclosure, for T3-4 Small enclosure, degree of protection IP65, glass-fiber reinforced polycarbonate, enclosure base RAL 9005, black/operator only RAL 7035, light gray, hard metric cable entry knockouts top, bottom, in the back plate, indicator light L-. can be mounted in base knock-out M20/M25, for T3-../Z switch, 3-4 contact units

Automation > Empty enclosure for switchgear
Insulating Enclosures

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Eaton Moeller CI-K2H-T3-4 Insulated enclosure, for T3-4 functions as a dedicated protective terminal box engineered to house specific cam switches and disconnectors securely in factory automation applications. Surface-mounted insulation boxes provide high ingress protection, safeguarding switching mechanisms from aggressive workshop atmospheres and accidental interference. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Housing material (EF001596): Plastic
  • Width (EF000008): 100 mm
  • Height (EF000040): 100 mm
  • Depth (EF000049): 181 mm
  • With transparent cover (EF001094): No
  • Suitable for emergency stop (EF001433): No
  • Model (EF000010): Surface mounting
  • Degree of protection (IP) (EF005474): IP65
  • Degree of protection (NEMA) (EF011959): 12

More info

▲

General specifications

Product Name
Eaton Moeller® series CI-K Insulated enclosure
Catalog Number
105859
Model Code
CI-K2H-T3-4
EAN
4015081056361
Product Length/Depth
181 mm
Product Height
100 mm
Product Width
100 mm
Product Weight
0.36 kg
Compliances
CE
Catalog Notes
1 contact unit = 2 contacts

Product specifications

Type
Insulated enclosure
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
Metric knockouts
Additional terminal
Enclosure material
Plastic
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
18.5 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
Degree of protection
IP65
NEMA 12
Model
Surface mounting
Radiated heat dissipation with separate mounting
18.5 W (at an ambient temperature of 20 °C)

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.