1 Pcs.

Housing, IP23_x, HxWxD=192x184x160mm, for transformer. Can only be sold assembled. +IP23/30 IP23 enclosures, For use with DTZ0.1 … DTZ0.16 IP23 enclosure for DTZ0.1 to DTZ0.16, enclosure can be used with primary or secondary voltage of 42 V to max, 1000 V including tapping

Automation > Empty enclosure for switchgear
Transformers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Eaton Moeller housing (+IP23/30) is a robust steel enclosure engineered to house industrial transformers and protect them from ambient hazards in built-in electrical assemblies. Protective housings of this type ensure adequate mechanical shielding and maintain necessary airflow requirements for power control units. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Housing material (EF001596): Steel
  • Width (EF000008): 160 mm
  • Height (EF000040): 184 mm
  • Depth (EF000049): 192 mm
  • With transparent cover (EF001094): No
  • Suitable for emergency stop (EF001433): No
  • Model (EF000010): Built-in
  • Degree of protection (IP) (EF005474): IP23

More info

▲

General specifications

Product Name
Eaton Moeller® series Accessory Housing
Catalog Number
200706
Model Code
+IP23/30
EAN
4015082007065
Product Length/Depth
192 mm
Product Height
184 mm
Product Width
160 mm
Product Weight
4.9 kg
Compliances
CE
Catalog Notes
Electrical characteristics: all details for no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values relate to a temperature of 20 °C

Features & Functions

Enclosure material
Steel
Features
Separate windings

General

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Duty factor
100 %
Insulation class
B
F
Model
Built-in
Product category
Accessories

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
28 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
Radiated heat dissipation with separate mounting
28 W (at an ambient temperature of 20 °C)
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.