View larger
Images are for illustrative purposes only. Please refer to data sheet for details
HN-C32/2 194874 Y7-194874 EATON ELECTRIC Miniature Circuit breaker 2-pole C-char 32-A
HN-C32/2
194874
Y7-194874
EATON - MOELLER
1 Pcs.
Miniature Circuit breaker 2-pole C-char 32-A
HN-C32/2
Eaton Moeller series xPole Home - HN/HN-HX MCB. HN, xPole Home, 2-pole, tripping characteristic: C, rated current In: 32 A, rated switching capacity IEC/EN 60898-1: 6 kA
Miniature circuit breaker (MCB), HN, xPole Home, 2-pole, tripping characteristic: C, rated current In: 32 A, rated switching capacity according to IEC/EN 60898-1: 6 kA, Switchgear for residential and commercial applications
Automation > Miniature circuit breaker (MCB)
Home Switchgear
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
HN-C32/2 is an Eaton Moeller miniature circuit breaker designed to safeguard residential or commercial electrical circuits from overloads and short-circuit faults.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller series xPole Home - HN/HN-HX MCB
- Catalog Number: 194874
- Model Code: HN-C32/2
- EAN: 9010238063587
- Product Length/Depth: 85 mm
- Product Height: 73 mm
- Product Width: 35.4 mm
- Product Weight: 0.24 kg
- Compliances: RoHS conform
- Number of poles: Two-pole
- Number of poles (total): 2
- Number of poles (protected): 2
- Tripping characteristic: C
- Release characteristic: C
- Amperage Rating: 32 A
- Type: HN Miniature circuit breaker
More info
▲General specifications
| Product Name | Eaton Moeller series xPole Home - HN/HN-HX MCB |
| Catalog Number | 194874 |
| Model Code | HN-C32/2 |
| EAN | 9010238063587 |
| Product Length/Depth | 85 mm |
| Product Height | 73 mm |
| Product Width | 35.4 mm |
| Product Weight | 0.24 kg |
| Compliances | RoHS conform |
Delivery program
| Application |
|
| Number of poles | Two-pole |
| Number of poles (total) | 2 |
| Number of poles (protected) | 2 |
| Tripping characteristic | C |
| Release characteristic | C |
| Amperage Rating | 32 A |
| Type |
|
Technical Data - Electrical
| Voltage type | AC |
| Rated operational voltage (Ue) - max | 230 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Frequency rating - min | 50 Hz |
| Frequency rating - max | 60 Hz |
| Rated switching capacity (IEC/EN 60898-1) | 6 kA |
| Overvoltage category | III |
| Pollution degree | 3 |
Technical Data - Mechanical
| Width in number of modular spacings | 2 |
| Built-in depth | 44 mm |
| Degree of protection | IP20 |
| Connectable conductor cross section (solid-core) - min | 1 mm² |
| Connectable conductor cross section (solid-core) - max | 25 mm² |
| Connectable conductor cross section (multi-wired) - min | 1 mm² |
| Connectable conductor cross section (multi-wired) - max | 25 mm² |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 32 A |
| Heat dissipation per pole, current-dependent | 0 W |
| Equipment heat dissipation, current-dependent | 8.1 W |
| Static heat dissipation, non-current-dependent | 0 W |
| Heat dissipation capacity | 0 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 75 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Current limiting class | 3 |
| Features | Additional equipment possible |
| Special features | Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity |
| Suitable for | Flush-mounted installation |
| Used with | HN Miniature circuit breaker |