EATON - MOELLER SPX300A2-5A4N1 SPX300A2-5A4N1 125421 EATON ELECTRIC Variable frequency drive SPX 3-/3-phase 690 V 315 kW dynamic vector con.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SPX300A2-5A4N1 125421 EATON ELECTRIC Variable frequency drive SPX 3-/3-phase 690 V 315 kW dynamic vector con..

SPX300A2-5A4N1

125421

EATON - MOELLER

1 Pcs.

Variable frequency drive SPX 3-/3-phase 690 V 315 kW ; dynamic vector control; protection type IP54; integrated EMC filter; with input fuse Frequency converter; High performance; 385 A; 355 kW; IP54; 690 V AC; Class C3 EMC Filter Variable frequency drive, 600 V AC, 3-phase, 315 kW, IP54, Radio interference suppression filter, OLED display, FR10

Automation > Frequency converter less than 1 kV
Eaton Frequency Converters

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton SPX variable frequency drive
Catalog Number
125421
Model Code
SPX300A2-5A4N1
EAN
4015081230273
Product Length/Depth
602 mm
Product Height
2140 mm
Product Width
595 mm
Product Weight
275 kg
Certifications
UL File No.: E134360
CE
DNV
RCM
IEC/EN61800-3
IEC/EN61800-5
RoHS, ISO 9001
Specification for general requirements: IEC/EN 61800-2
UL report applies to both US and Canada
CSA Class No.: 3211-06
IEC/EN 61800-3
Safety: EN 61800-5-1: 2003
UL
CSA-C22.2 No. 14
UL 508C
UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8
Certified by UL for use in Canada
CUL

General

Degree of protection
IP54
NEMA 12
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Fitted with:
OLED display
PC connection
Control unit
DC link choke
IGBT inverter
Internal DC link
Radio interference suppression filter
Frame size
FR10
Functions
4-quadrant operation possible
Mounting position
Vertical
Product Category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference class
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Suitable for
Branch circuits, (UL/CSA)

Climatic environmental conditions

Altitude
Above 1000 m with 1 % performance reduction per 100 m
Max. 1000 m
Max. 3000 m
Ambient operating temperature - min
-10 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature at 150% overload - min
-10 °C
Ambient operating temperature at 150% overload - max
50 °C
Ambient storage temperature - min
-40 °C
Climatic proofing
< 95 % relative humidity, no condensation, no corrosion, no dripping water

Main circuit

Mains voltage - min
525 V
Mains voltage - max
690 V
Operating mode
U/f control
Optional: Vector control with feedback (CLV)
Sensorless vector control (SLV)
Output frequency - min
0 Hz
Output frequency - max
320 Hz
Output voltage (U2)
600 V AC, 3-phase
690 V AC, 3-phase
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
45 Hz
Rated frequency - max
66 Hz
Rated operational current (Ie) at 110% overload
385 A
Rated operational current (Ie) at 150% overload
325 A
Rated operational power at 690 V, 50 Hz, 3-phase
315 kW
Rated operational power at 690 V, 50 Hz, 3-phase, 110% overload
355 kW
Rated operational voltage
690 V AC, 3-phase
600 V AC, 3-phase
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Supply frequency
50/60 Hz
Switching frequency
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
System configuration type
AC supply systems with earthed center point
Voltage rating - max
690 VAC

Motor rating

Assigned motor current IM at 690 V, 50 Hz, 150% overload
316 A
Assigned motor current IM at 690 V, 60 Hz, 110% overload
332 A
Assigned motor current IM at 690 V, 60 Hz, 150% overload
251 A
Assigned motor power at 690 V, 60 Hz, 3-phase
300 HP
Assigned motor power at 690 V, 60 Hz, 3-phase, 110 % overload
400 HP

Control circuit

Number of inputs (analog)
2
Number of inputs (digital)
6
Number of outputs (analog)
1
Number of outputs (digital)
1
Number of relay outputs
2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
Rated control voltage (Uc)
24 V DC (external, max. 250 mA)

Communication

Communication interface
Modbus-TCP, optional
PROFIBUS-DP
CANopen®, optional
DeviceNet, optional
LonWorks, optional
BACnet/IP, optional
BACnet MS/TP, optional
EtherCAT, optional
Ethernet IP, optional
Modbus-RTU, optional
PROFINET, optional
Connection to SmartWire-DT
No
Protocol
DeviceNet
TCP/IP
PROFIBUS
Other bus systems
LON
Data-Highway
CAN

Design verification

Equipment heat dissipation, current-dependent Pvid
7875 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
325 A
Static heat dissipation, non-current-dependent Pvs
0 W
Heat dissipation details
Operation (with 150 % overload)
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.