View larger
DA1-32150FB-B55C 169371 Y7-169371 EATON ELECTRIC Variable frequency drive, 230 V AC, 3-phase, 150 A, 45 kW, ..
DA1-32150FB-B55C
169371
Y7-169371
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered by Eaton Moeller, part reference DA1-32150FB-B55C is a variable frequency drive utilized for precise rotational speed control in demanding industrial motor applications.
Variable frequency drives regulate AC motor velocity and torque, allowing facilities to match mechanical output precisely to production demands while improving energy efficiency. Final pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 200 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 250 V
- Nominal output current I2N (EF009561): 150 A
- Power consumption (EF000346): 814 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 2
- Number of analogue inputs (EF001994): 2
- Number of digital outputs (EF001993): 2
- Number of digital inputs (EF001992): 5
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN61800-3
Specification for general requirements: IEC/EN 61800-2
UL
UL report applies to both US and Canada
CSA-C22.2 No. 14
CUL
CE
Safety: EN 61800-5-1: 2003
UkrSEPRO
UL 508C
DNV
RCM
UL Category Control No.: NMMS, NMMS7
IEC/EN 61800-3
IEC/EN61800-5
EAC
UL File No.: E172143
RoHS, ISO 9001
General
C2 ≤ 5 m, Radio interference level, maximum motor cable length
100 m, screened, maximum permissible, Motor feeder
200 m, screened, with motor choke, maximum permissible, Motor feeder
C3 ≤ 25 m, Radio interference level, maximum motor cable length
300 m, unscreened, with motor choke, maximum permissible, Motor feeder
PROFIBUS, optional
SmartWire-DT, optional
OP-Bus (RS485), built in
Modbus-TCP, optional
Ethernet IP, optional
EtherCAT, optional
Modbus RTU, built in
CANopen®, built in
DeviceNet, optional
Yes
NEMA 12
DC link choke
Brake chopper
Control unit
Additional PCB protection
Breaking resistance
IGBT inverter
Internal DC link
PC connection
Radio interference suppression filter
EtherNet/IP
PROFIBUS
CAN
MODBUS
Other bus systems
DeviceNet
TCP/IP
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Climatic environmental conditions
Max. 4000 m
Above 1000 m with 1 % derating per 100 m
Main circuit
1430 W at 100% current and 90% speed
350 W at 25% current and 0% speed
490 W at 25% current and 50% speed
490 W at 50% current and 0% speed
640 W at 50% current and 50% speed
790 W at 50% current and 90% speed
960 W at 100% current and 0% speed
Optional: Vector control with feedback (CLV)
Speed control with slip compensation
Sensorless vector control (SLV)
230 V AC, 3-phase
240 V AC, 3-phase
Motor rating
Apparent power
Braking function
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit