View larger
DA1-127D0FB-B66C 169349 Y7-169349 EATON ELECTRIC Variable frequency drive, 230 V AC, 1-phase, 7 A, 1.5 kW, I..
DA1-127D0FB-B66C
169349
Y7-169349
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller variable frequency drive, reference DA1-127D0FB-B66C, alters motor speed dynamically to align mechanical output with specific production line requirements. These electronic controllers safeguard machinery by ensuring smooth acceleration profiles and steady torque regulation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 200 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 1
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 250 V
- Nominal output current I2N (EF009561): 7 A
- Power consumption (EF000346): 63 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 2
- Number of analogue inputs (EF001994): 2
- Number of digital outputs (EF001993): 2
- Number of digital inputs (EF001992): 5
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
CSA-C22.2 No. 14
Safety: EN 61800-5-1: 2003
UL
IEC/EN61800-5
CUL
UL File No.: E172143
UL 508C
UL report applies to both US and Canada
Specification for general requirements: IEC/EN 61800-2
UkrSEPRO
IEC/EN 61800-3
EAC
CE
UL Category Control No.: NMMS, NMMS7
RCM
Certified by UL for use in Canada
RoHS, ISO 9001
General
C1 ≤ 1 m, Radio interference level, maximum motor cable length
C3 ≤ 25 m, Radio interference level, maximum motor cable length
100 m, screened, maximum permissible, Motor feeder
300 m, unscreened, with motor choke, maximum permissible, Motor feeder
200 m, screened, with motor choke, maximum permissible, Motor feeder
C2 ≤ 5 m, Radio interference level, maximum motor cable length
Modbus-TCP, optional
PROFINET, optional
EtherCAT, optional
CANopen®, built in
PROFIBUS, optional
OP-Bus (RS485), built in
DeviceNet, optional
Ethernet IP, optional
IP66
OLED display
Radio interference suppression filter
Breaking resistance
Brake chopper
PC connection
Internal DC link
Additional PCB protection
IGBT inverter
MODBUS
EtherNet/IP
CAN
PROFINET IO
Other bus systems
DeviceNet
TCP/IP
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Climatic environmental conditions
Max. 1000 m
Above 1000 m with 1 % derating per 100 m
Main circuit
38 W at 25% current and 50% speed
39 W at 50% current and 0% speed
46 W at 50% current and 50% speed
54 W at 50% current and 90% speed
55 W at 100% current and 0% speed
66 W at 100% current and 50% speed
77 W at 100% current and 90% speed
U/f control
Sensorless vector control (SLV)
Speed control with slip compensation
230 V AC, 3-phase
230 V AC, 1-phase
Motor rating
Apparent power
Braking function
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit