View larger
FRCMM-63/4/03-S 170327 Y7-170327 EATON ELECTRIC Residual-current circuit breaker trip block for PLS. 40A, 4 ..
FRCMM-63/4/03-S
170327
Y7-170327
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Tertiary and Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller FRCMM-63/4/03-S is a residual-current circuit breaker trip block designed to integrate with modular circuit protection assemblies. Such components monitor current differentials in commercial and industrial electrical distribution setups to protect against earth faults.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 63 A
- Rated fault current (EF002358): 0.3 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): AC
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50/60 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
EN45545-2
IEC 61373
Delivery program
40 ms delayed - selective switch off
- FRCmM
- Residual current circuit breakers
- Type S
Technical data - electrical
Technical data - mechanical
DIN rail
IP20, IP40 with suitable enclosure
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Additional equipment possible
Selective protection
- Current test marks as per inscription
- Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
Type S
Residual current circuit breakers