View larger
FRCMM-63/4/01-S 170323 Y7-170323 EATON ELECTRIC Circuit breaker, 63A, 4p, 100mA, S-class
FRCMM-63/4/01-S
170323
Y7-170323
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Tertiary and Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An FRCMM-63/4/01-S 170323 Y7-170323 EATON ELECTRIC Circuit breaker, 63A, 4p, 100mA, S-class provides essential fault protection by monitoring electrical circuits for ground leakage imbalances. These components are routinely integrated into electrical distribution panels to prevent hazardous touch voltages and reduce fire risks in complex facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 63 A
- Rated fault current (EF002358): 0.1 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): AC
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50/60 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
EN45545-2
IEC 61373
Delivery program
40 ms delayed - selective switch off
- FRCmM
- Residual current circuit breakers
- Type S
Technical data - electrical
Technical data - mechanical
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
IP20
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Selective protection
Additional equipment possible
- Current test marks as per inscription
- Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
Residual current circuit breakers
Type S