View larger
FRCMM-40/4/01-G/A 170301 Y7-170301 EATON ELECTRIC Residual current circuit breaker (RCCB), 40A, 4p, 100mA, t..
FRCMM-40/4/01-G/A
170301
Y7-170301
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Tertiary and Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller FRCMM-40/4/01-G/F is a residual current circuit breaker designed to monitor electrical loads and disconnect power instantly during earth leakage events. These breakers are installed in industrial and commercial enclosures to protect wiring infrastructure and personnel. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 40 A
- Rated fault current (EF002358): 0.1 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): No
- Short-time delayed tripping (EF003604): Yes
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 3 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50/60 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
EN45545-2
IEC 61373
IEC/EN 61008
Delivery program
10 ms delayed
- FRCmM
- Residual current circuit breakers
- Type G/A (ÖVE E 8601)
Technical data - electrical
Technical data - mechanical
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
IP20, IP40 with suitable enclosure
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Residual current circuit breaker
- Current test marks as per inscription
- Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
FRCmM
Type G/A (ÖVE E 8601)