View larger
FRCMM-125/4/05-S/BFQ 171191 Y7-171191 EATON ELECTRIC AC/DC sensitive residual current circuit-breakers, 125A..
FRCMM-125/4/05-S/BFQ
171191
Y7-171191
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller FRCMM-125/4/05-S/BFQ is an AC/DC sensitive residual current circuit-breaker engineered to protect electrical installations against earth leakage faults and insulation failures. Residual current devices continuously monitor current balance in multi-wire circuits, disconnecting the supply instantly when an imbalance exceeds safe thresholds to prevent equipment damage and electrical shock hazards.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 125 A
- Rated fault current (EF002358): 0.5 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): B
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
IEC/EN 62423
Delivery program
50 ms delayed, selective switch off
Technical data - electrical
Technical data - mechanical
DIN rail
IP20
1.5 mm² - 16 mm² (2x)
1.5 mm² - 5 mm²
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Residual current circuit breaker
Selective protection
- Current test marks as per inscription
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.2% for every 1 °C
Type S/Bfq
FRCmM-125