View larger
FRCMM-125/4/05-S/A 171183 Y7-171183 EATON ELECTRIC Residual current circuit breaker (RCCB), 125A, 4p, 500mA,..
FRCMM-125/4/05-S/A
171183
Y7-171183
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for heavy-duty electrical installations, the Eaton Moeller FRCMM-125/4/05-S/A residual current circuit breaker safely isolates power circuits during earth leakage events to prevent equipment damage and user injury.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 125 A
- Rated fault current (EF002358): 0.5 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
Delivery program
Selective switch off
- FRCmM-125
- Residual current circuit breakers
- Type S/A
Technical data - electrical
Technical data - mechanical
DIN rail
IP20, IP40 with suitable enclosure
1.5 mm² - 16 mm² (2x)
1.5 mm² - 5 mm²
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Additional equipment possible
Residual current circuit breaker
- Current test marks as per inscription
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.2% for every 1 °C
FRCmM-125
Residual current circuit breakers