A digital residual current circuit-breaker from Eaton Moeller delivers advanced earth leakage protection and system monitoring for heavy-duty electrical installations. Designed for high-capacity distribution networks, this protective device interrupts power promptly when insulation faults or ground currents exceed safe parameters.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 125 A
- Rated fault current (EF002358): 0.03 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): No
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 0.25 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
Delivery program
250 A (8/20 μs) surge-proof
- FRCmM-125
- Residual current circuit breakers
- Type A
Technical data - electrical
Technical data - mechanical
DIN rail
IP20
1.5 mm² - 50 mm²
1.5 mm² - 16 mm² (2x)
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Additional equipment possible
- Current test marks as per inscription
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.2% for every 1 °C
Type A