View larger
FRCMM-100/4/03-U 170467 EATON ELECTRIC Digital residual current circuit-breaker, 63A, 4p, 300mA, type U
FRCMM-100/4/03-U
170467
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The FRCMM-100/4/03-U 170467 EATON ELECTRIC Digital residual current circuit-breaker, 63A, 4p, 300mA, type U is a digital residual current circuit-breaker built to monitor electrical networks for differential faults and protect against earth leakage hazards. RCCBs provide indispensable safety isolation in complex distribution boards, preventing electrical shock and mitigating potential fire risks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 100 A
- Rated fault current (EF002358): 0.3 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50/60 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
Delivery program
40 ms delayed - selective switch off
Technical data - electrical
4 kV (1.2/50 µs)
50 Hz
Technical data - mechanical
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
IP20, IP40 with suitable enclosure
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Selective protection
Residual current circuit breaker
- Current test marks as per inscription
- Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C
FRCmM
Type U