View larger
FRCmM-100/4/003-A-400 304194 Y7-304194 EATON ELECTRIC Residual current circuit breaker (RCCB), 100 A, 4 p, 3..
FRCmM-100/4/003-A-400
304194
Y7-304194
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A residual current circuit breaker (RCCB) by Eaton Moeller, part number FRCmM-100/4/003-A-400, protects personnel and equipment against earth leakage faults in modern low-voltage electrical installations. These protective devices automatically disconnect a circuit when a residual current exceeds a predetermined threshold, preventing hazardous shock conditions.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 100 A
- Rated fault current (EF002358): 0.03 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): No
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 0.25 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): No
- Frequency (EF005455): 50/60 Hz
- Additional equipment possible (EF008148): No
More info
▲General specifications
EN45545-2
IEC 61373
Delivery program
Partly surge-proof 250 A
- FRCmM
- Residual current circuit breakers
- Type A
Technical data - electrical
Technical data - mechanical
DIN rail
IP20
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
- Current test marks as per inscription
- Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C