FRCMM-100/2/03-A 304065 Y7-304065 EATON ELECTRIC Residual current circuit breaker (RCCB), 100A, 2p, 300mA, t..
FRCMM-100/2/03-A
304065
Y7-304065
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for industrial power distribution, this Eaton Moeller FRCMM-100/2/03-A residual current circuit breaker (RCCB) senses leakage currents to protect operators and hardware. It provides reliable interruption during ground fault conditions to maintain installation safety standards. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB
- Catalog Number: 304065
- Model Code: FRCMM-100/2/03-A
- EAN: 9010238194267
- Product Length/Depth: 76 mm
- Product Height: 80 mm
- Product Width: 35 mm
- Product Weight: 0.201 kg
- Compliances: RoHS conform
- Certifications: IEC/EN 61008 EN45545-2 IEC 61373
- Number of poles: Two-pole
- Tripping time: Non-delayed
- Amperage Rating: 100 A
- Rated short-circuit strength: 10 kA with back-up fuse
- Fault current rating: 300 mA
- Sensitivity type: Pulse-current sensitive
More info
▲General specifications
| Product Name | Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB |
| Catalog Number | 304065 |
| Model Code | FRCMM-100/2/03-A |
| EAN | 9010238194267 |
| Product Length/Depth | 76 mm |
| Product Height | 80 mm |
| Product Width | 35 mm |
| Product Weight | 0.201 kg |
| Compliances | RoHS conform |
| Certifications | IEC/EN 61008 EN45545-2 IEC 61373 |
Delivery program
| Application |
|
| Number of poles | Two-pole |
| Tripping time | Non-delayed |
| Amperage Rating | 100 A |
| Rated short-circuit strength | 10 kA with back-up fuse |
| Fault current rating | 300 mA |
| Sensitivity type | Pulse-current sensitive |
| Impulse withstand current | 250 A (8/20 μs) surge-proof Partly surge-proof 250 A |
| Type |
|
Technical Data - Electrical
| Voltage rating (IEC/EN 60947-2) | 240 V AC |
| Rated operational voltage (Ue) - max | 240 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated fault current - min | 0.3 A |
| Rated fault current - max | 0.3 A |
| Frequency rating | 50 Hz / 60 Hz |
| Short-circuit rating | 80 A (max. admissible back-up fuse) |
| Leakage current type | A |
| Rated residual making and breaking capacity | 1000 A |
| Admissible back-up fuse overload - max | 80 A gG/gL |
| Rated short-time withstand current (Icw) | 10 kA |
| Surge current capacity | 0.25 kA |
| Test circuit range | 184 V AC - 250 V AC |
| Pollution degree | 2 |
| Lifespan, electrical | 4000 operations |
Technical Data - Mechanical
| Frame | 45 mm |
| Width in number of modular spacings | 2 |
| Built-in width (number of units) | 35 mm (2 SU) |
| Built-in depth | 70.5 mm |
| Mounting Method | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 DIN rail |
| Mounting position | As required |
| Degree of protection | IP20 IP20, IP40 with suitable enclosure |
| Status indication | White / blue |
| Terminals (top and bottom) | Twin-purpose terminals |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Terminal capacity (cable) | M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2) |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Contact position indicator color | Red / green |
| Tightening torque | 2 Nm - 2.4 Nm |
| Busbar material thickness | 0.8 mm - 2 mm |
| Lifespan, mechanical | 20000 operations |
| Permitted storage and transport temperature - min | -35 °C |
| Permitted storage and transport temperature - max | 60 °C |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 100 A |
| Heat dissipation per pole, current-dependent | 9.4 W |
| Equipment heat dissipation, current-dependent | 13.6 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 75 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Features | Additional equipment possible Residual current circuit breaker |
| Special features |
|
| Used with | FRCmM Type A Residual current circuit breakers |