View larger
FRCDM-40/4/03-S/A 168637 Y7-168637 EATON ELECTRIC Digital residual current circuit-breaker, 40A, 4p, 300mA, ..
FRCDM-40/4/03-S/A
168637
Y7-168637
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A digital residual current circuit-breaker, such as the Eaton Moeller FRCDM-40/4/03-S/A, provides robust protection against earth faults in commercial and industrial electrical setups. The unit automatically disconnects circuits when leakage currents exceed safe operating limits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 415 V
- Rated current (EF000227): 40 A
- Rated fault current (EF002358): 0.3 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): A
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
EN45545-2
IEC 61373
Delivery program
40 ms delayed - selective switch off
- FRCdM
- Residual current circuit-breakers, digital
- Type S/A
Technical data - electrical
Technical data - electrical - dry auxiliary contact
Technical data - mechanical
DIN rail
IP20
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Residual current circuit-breakers, digital
Selective protection
- Current test marks as per inscription
- Dry auxiliary contact: > 100,000 electrical switching operations per minute at 2 A 30 VDC resistive load
- Dry auxiliary contact: > 5 x 100,000 electrical switching operations per minute at 1 A 30 VDC resistive load
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
Residual current circuit-breakers, digital
Type S/A