EATON - MOELLER FRBMM-B16/3/003-A-RT FRBMM-B16/3/003-A-RT 305153 Y7-305153 EATON ELECTRIC Combined Int. FRBMM, 16A, 30mA, B-Curve, 3p, Class A Ri.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FRBMM-B16/3/003-A-RT 305153 Y7-305153 EATON ELECTRIC Combined Int. FRBMM, 16A, 30mA, B-Curve, 3p, Class A Ri..

FRBMM-B16/3/003-A-RT

305153

Y7-305153

EATON - MOELLER

1 Pcs.

Combined Int. FRBMM, 16A, 30mA, B-Curve, 3p, Class A Ring Terminal RCD/MCB, 16A, 30mA, miniature circuit-breaker trip curve: B, 3pole, residual current circuit-breaker trip characteristic: A

Automation > Earth leakage circuit breaker
Modular Switchgear – Tertiary and Differential

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Operating as a combined residual current device, this Eaton Moeller FRBMM-B16/3/003-A-RT unit delivers integrated overcurrent protection and fault current detection for multi-phase electrical supplies. These units are typically deployed in demanding industrial switchgear to prevent equipment damage and ensure personnel safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of poles (total) (EF008618): 3
  • Number of protected poles (EF005548): 3
  • Rated voltage (EF000228): 415 V
  • Rated insulation voltage Ui (EF001366): 500 V
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Rated current (EF000227): 16 A
  • Rated fault current (EF002358): 0.03 A
  • Leakage current type (EF002560): A
  • Current limiting class (EF002568): 3
  • Disconnection characteristic (EF012587): Undelayed
  • Surge current capacity (EF002564): 0.25 kA
  • Voltage type (EF000187): AC
  • Frequency (EF005455): 50 Hz
  • Release characteristic (EF000889): B
  • Concurrently switching neutral conductor (EF005997): No
  • With interlocking device (EF007385): No

More info

▲
RCD/MCB, 16A, 30mA, miniature circuit-breaker trip curve: B, 3pole, residual current circuit-breaker trip characteristic: A

General specifications
Product name
Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection
Part no.
FRBMM-B16/3/003-A-RT
EAN
9010238988392
Product Length/Depth
75.5 millimetre
Product height
84.5 millimetre
Product width
70.8 millimetre
Product weight
0.39 kilogram
Compliances
RoHS conform
Certifications
IEC 61373
EN45545-2
Product Tradename
xEffect - FRBm6/M
Product Type
RCBO - Residual-current circuit breaker with overcurrent protection
Product Sub Type
None
Globally Marketable
Yes
Delivery program
Number of poles (protected)
3
Number of poles (total)
3
Release characteristic
B
Amperage Rating
16 A
Rated current
16 A
Fault current rating
0.03 A
Technical Data - Electrical
Voltage type
AC
Rated operational voltage (Ue) - max
415 V
Rated insulation voltage (Ui)
500 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating
50 Hz
Leakage current type
A
Rated switching capacity (IEC/EN 60947-2)
15 kA
Rated short-circuit breaking capacity (EN 60947-2)
15 kA
Rated short-circuit breaking capacity (EN 61009)
10 kA
Rated short-circuit breaking capacity (EN 61009-1)
10 kA
Rated short-circuit breaking capacity (IEC 60947-2)
15 kA
Surge current capacity
0.25 kA
Disconnection characteristic
Undelayed
Pollution degree
2
Technical Data - Mechanical
Width in number of modular spacings
4
Built-in depth
75.5 mm
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Additional information
Current limiting class
3

Technical data ETIM 8.0

Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination ([email protected] [AFZ810015])
Number of poles (total)
3
Number of protected poles
3
Rated voltage
415 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity according to EN 61009
10 kA
Rated short-circuit breaking capacity according to IEC 60947-2
15 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
10 kA
Disconnection characteristic
Undelayed
Surge current capacity
0.25 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
B
Concurrently switching neutral conductor
No
With interlocking device
No
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
-25 - 40 °C
Width in number of modular spacings
4
Built-in depth
75.5 mm
Flush-mounted installation
No
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.