EATON - MOELLER FRBDM-D16/1N/003-G/A FRBDM-D16/1N/003-G/A 168276 Y7-168276 EATON ELECTRIC RCD/MCB comb. switch, 16A, 30mA, miniature circuit-br. .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FRBDM-D16/1N/003-G/A 168276 Y7-168276 EATON ELECTRIC RCD/MCB comb. switch, 16A, 30mA, miniature circuit-br. ..

FRBDM-D16/1N/003-G/A

168276

Y7-168276

EATON - MOELLER

1 Pcs.

RCD/MCB comb. switch, 16A, 30mA, miniature circuit-br. type D trip characteristic, 1-phase+N, residual current circuit-br. trip characteristic: A FRBDM-D16/1N/003-G/A Eaton Moeller series xEffect - FRBdM RCBO - residual-current circuit breaker with overcurrent protection. RCD/MCB, 16A, 30mA, MCB trip type D, 1-phase+N, RCCB trip type: A High-quality residual current device/miniature circuit breaker combination, line voltage-dependent, contact position indicator red - green, terminal rear plug protection, tri-stable slide catch - enables removal from existing busbar system, comprehensive range of accessories suitable for subsequent installation, wide range of rated fault currents, rated operational currents up to 40 A, tripping characteristics B, C, D, rated breaking capacity 10 kA, suitable for outdoor use (on-site power and outdoor distribution board) up to -25 °C

Automation > Earth leakage circuit breaker
Modular Switchgear – Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Providing integrated circuit protection, the Eaton Moeller FRBDM-D16/1N/003-G/A RCD/MCB comb. switch prevents damage from overcurrents while detecting residual current faults. Such devices are essential components for electrical distribution panels requiring high operational reliability. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of poles (total): 2
  • Number of protected poles: 1
  • Rated voltage: 240 V
  • Rated insulation voltage Ui: 250 V
  • Rated impulse withstand voltage Uimp: 4 kV
  • Rated current: 16 A
  • Rated fault current: 0.03 A
  • Leakage current type: A
  • Current limiting class: 3
  • Power loss: 4.3 W
  • Disconnection characteristic: Short-time delayed
  • Surge current capacity: 3 kA
  • Voltage type: AC
  • Frequency: 50 Hz
  • Release characteristic: D
  • Concurrently switching neutral conductor: Yes

More info

▲

General specifications

Product Name
Eaton Moeller series xEffect - FRBdM RCBO - residual-current circuit breaker with overcurrent protection
Catalog Number
168276
Model Code
FRBDM-D16/1N/003-G/A
EAN
4015081648085
Product Length/Depth
86 mm
Product Height
75 mm
Product Width
37 mm
Product Weight
0.25 kg
Compliances
CE Marked
RoHS conform
Certifications
CE

Delivery Program

Basic function
Combined RCD/MCB devices
Number of poles
Single-pole + N
Tripping
Short time-delayed
Tripping characteristic
D
Application
Switchgear for industrial and advanced commercial applications
Rated switching capacity (IEC/EN 61009)
10 kA
Type
RCBO
Product range
FRBdM
Impulse withstand current
Surge-proof, 3 kA

Technical Data - Electrical

Rated operational voltage (Ue) - max
240 V
Sensitivity type
Pulse-current sensitive
Rated current
16 A

Technical Data

Number of poles (total)
2
Number of poles (protected)
1
Rated impulse withstand voltage (Uimp)
4 kV
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity (EN 61009)
10 kA
Rated short-circuit breaking capacity (EN 61009-1)
10 kA
Rated short-circuit breaking capacity (EN 60947-2)
0 kA
Disconnection characteristic
Short-time delayed
Surge current capacity
3 kA
Voltage type
AC
Release characteristic
D
Overvoltage category
III
Pollution degree
2

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.