EATON - MOELLER BP-F-600/17/3 BP-F-600/17/3 102057 0002459174 EATON ELECTRIC Floor standing distribution board with three-point turn-lock,.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

BP-F-600/17/3 102057 0002459174 EATON ELECTRIC Floor standing distribution board with three-point turn-lock,..

BP-F-600/17/3

102057

0002459174

EATON - MOELLER

1 Pcs.

Floor standing distribution board with three-point turn-lock, W = 600 mm, H = 1760 mm, D = 300 mm Floor standing distribution board with cam lock, IP30, gray, RAL 7035, width 600 mm, outside height 1760 mm, front plate height 1650 mm, depth of 300 mm, incl. gland plate inserts at the top and bottom, metal door with cam lock, door can be right-hand or left-hand door, if using an MSW assembly configuration, 2 pairs of BPZ-CTS-S corner towers and 1 BPZ-SNAP-MSW-CTS snap fitting element will be additionally required, if using a base frame assembly configuration, 2 BPZ-FPS front plate supports will be additionally required . indoor installation with MSW or mounting towers possible, earthed metal covers, extraordinary stability as a result of welded construction, ample wiring area, variable interior fittings with / without removable mounting frame, well-structured, multilayered design for easily accessible installation: base frame - DIN-rails ... - enclosure

Automation > Enclosure/switchgear cabinet (empty)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

This Eaton Moeller BP-F-600/17/3 floor standing distribution board provides a secure, structured housing solution for electrical control gear and distribution components in industrial environments. Enclosures of this type are widely utilized in commercial and manufacturing facilities to centralize power management while protecting sensitive equipment from external hazards.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Width (EF000008): 615 mm
  • Height (EF000040): 1780 mm
  • Depth (EF000049): 315 mm
  • Material (EF002169): Steel
  • Surface finishing (EF006569): Powder coating
  • Colour (EF000007): Grey
  • RAL-number (EF000116): 7035
  • Freestanding (EF020363): true
  • Floor standing wall model (EF015208): false
  • Suitable for wall mounting (EF000664): false
  • Corner model (EF020814): false
  • Intermediate mounting (EF022994): false
  • Couplable (EF001229): false
  • With mounting plate (EF000118): false
  • Mounting plate depth-adjustable (EF006054): true
  • Suitable for wall built-in (EF007536): false

More info

▲

General specifications

Product Name
Eaton xEnergy Basic empty enclosure
Catalog Number
102057
Model Code
BP-F-600/17/3
EAN
4015081022052
Product Length/Depth
315 mm
Product Height
1780 mm
Product Width
615 mm
Product Weight
40 kg
Compliances
RoHS conform

Delivery program

Type
Basic device
Application
Indoor (installation site)
Color
Gray
Light gray (RAL 7035)

Technical data - mechanical

Surface finishing
With powder coating
Powder coating
Mounting method
Floor standing distribution board
Detached
Material
Sheet steel
Steel
Material quality
Other
Number of connector holes
0
Number of covers/doors
1
Number of locks
1
Permissible load of the door(s) according to IEC 62208 - max
0 N
Permissible load of the enclosure according to IEC 62208 - max
0 N
Permissible load of the mounting plate according to IEC 62208 - max
0 N
Cover/door type
Three-point turn-lock
Grade material
Sheet steel
Installation type
Floor installation possible

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890)
126 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
112 W
Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890)
253 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
225 W
Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890)
148 W
Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890)
136 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
126 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
118 W
Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890)
297 W
Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890)
273 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
253 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
237 W
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890
0 W

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK07
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
EMC-version
Mounting plate depth-adjustable
Fitted with:
Door
Functions
Basic device
RAL-number
7035
Suitable for
Metrical mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.