View larger
FAZ6-C3/2 239098 Y7-239098 EATON ELECTRIC Miniature circuit breaker (MCB), 3A, 2 p, type C characteristic, 6..
FAZ6-C3/2
239098
Y7-239098
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear - Tertiary
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Maintain system integrity across commercial setups using this Eaton Moeller miniature circuit breaker (MCB), 3A, 2 p, type C characteristic, 6. MCB units protect electrical distribution systems by automatically cutting off current flow during overloads or short-circuit faults. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller series xEffect - FAZ6 MCB
- Catalog Number: 239098
- Model Code: FAZ6-C3/2
- EAN: 4015082390983
- Product Length/Depth: 85 mm
- Product Height: 73 mm
- Product Width: 35.4 mm
- Product Weight: 0.216 kg
- Compliances: RoHS conform
- Number of poles (total): 2
- Number of poles (protected): 2
- Release characteristic: C
- Amperage Rating: 3 A
- Voltage type: AC
- Voltage rating (IEC/EN 60898-1): 415 V
- Voltage rating (IEC/EN 60947-2): 400
More info
▲General specifications
| Product Name | Eaton Moeller series xEffect - FAZ6 MCB |
| Catalog Number | 239098 |
| Model Code | FAZ6-C3/2 |
| EAN | 4015082390983 |
| Product Length/Depth | 85 mm |
| Product Height | 73 mm |
| Product Width | 35.4 mm |
| Product Weight | 0.216 kg |
| Compliances | RoHS conform |
Delivery program
| Number of poles (total) | 2 |
| Number of poles (protected) | 2 |
| Release characteristic | C |
| Amperage Rating | 3 A |
Technical Data - Electrical
| Voltage type | AC |
| Voltage rating (IEC/EN 60898-1) | 415 V |
| Voltage rating (IEC/EN 60947-2) | 400 |
| Rated operational voltage (Ue) - max | 230 V |
| Operational voltage (IEC/EN 60947-2) - max | 400 V |
| Operational voltage at DC (EC/EN 60947-2) - max | 60 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Frequency rating - min | 50 Hz |
| Frequency rating - max | 60 Hz |
| Rated switching capacity (IEC/EN 60947-2) | 7.5 kA |
| Overvoltage category | III |
| Pollution degree | 2 |
Technical Data - Mechanical
| Width in number of modular spacings | 2 |
| Built-in depth | 70.5 mm |
| Connectable conductor cross section (solid-core) - min | 1 mm² |
| Connectable conductor cross section (solid-core) - max | 25 mm² |
| Connectable conductor cross section (multi-wired) - min | 1 mm² |
| Connectable conductor cross section (multi-wired) - max | 25 mm² |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 3 A |
| Equipment heat dissipation, current-dependent | 2.4 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 75 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Current limiting class | 3 |
| Features | Additional equipment possible |