EATON - MOELLER FAZ6-B40/2 FAZ6-B40/2 239092 Y7-239092 EATON ELECTRIC Miniature circuit breaker (MCB), 40A, 2 p, type B characteristic,.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FAZ6-B40/2 239092 Y7-239092 EATON ELECTRIC Miniature circuit breaker (MCB), 40A, 2 p, type B characteristic,..

FAZ6-B40/2

239092

Y7-239092

EATON - MOELLER

1 Pcs.

Miniature circuit breaker (MCB), 40A, 2 p, type B characteristic, 6 kA FAZ6-B40/2 FAZ6-B40/2. Miniature circuit breaker (MCB), 40 A, 2p, characteristic: B, 6 kA High-quality miniature circuit breaker for industrial applications and residential applications, contact position indicator red - green, guide for secure terminal connection, tri-stable slide catch - enables removal from existing busbar system, comprehensive range of accessories suitable for subsequent installation, rated currents up to 63 A, tripping characteristics B, C, D

Automation > Miniature circuit breaker (MCB)
Modular Switchgear - Tertiary

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The FAZ6-B40/2 239092 Y7-239092 EATON ELECTRIC Miniature circuit breaker (MCB), 40A, 2 p, type B characteristic,.. provides reliable automatic disconnection of electrical circuits when subjected to overcurrent or short-circuit conditions. These dual-pole protective devices are widely utilized in industrial automation panels and building distribution systems to safeguard wiring infrastructure.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Built-in depth (EF000218): 70.5 mm
  • Release characteristic (EF000889): B
  • Number of poles (total) (EF008618): 2
  • Number of protected poles (EF005548): 2
  • Rated current (EF000227): 40 A
  • Rated voltage (EF000228): 400 V
  • Rated insulation voltage Ui (EF001366): 440 V
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Voltage type (EF000187): AC
  • Frequency (EF000416): 50 Hz
  • Power loss (EF005387): 7.5 W
  • Current limiting class (EF002568): 3
  • Flush-mounted installation (EF007517): No
  • Concurrently switching neutral conductor (EF005997): No
  • Over voltage category (EF002569): 3
  • Pollution degree (EF002570): 2

More info

▲

General specifications

Product Name
Eaton Moeller series xEffect - FAZ6 MCB
Catalog Number
239092
Model Code
FAZ6-B40/2
EAN
4015082390921
Product Length/Depth
85 mm
Product Height
73 mm
Product Width
35.4 mm
Product Weight
0.216 kg
Compliances
RoHS conform

Delivery programme

Number of poles (total)
2
Number of poles (protected)
2
Release characteristic
B
Amperage Rating
40 A

Technical data - electrical

Voltage type
AC
Voltage rating (IEC/EN 60898-1)
415 V
Voltage rating (IEC/EN 60947-2)
400
Rated operational voltage (Ue) - max
400 V
Operational voltage (IEC/EN 60947-2) - max
400 V
Operational voltage at DC (EC/EN 60947-2) - max
60 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2)
7.5 kA
Rated service short-circuit breaking capacity (IEC/EN 60898-1)
6 kA
Rated service short-circuit breaking capacity (IEC/EN 60947-2)
10 kA
Rated short-circuit breaking capacity (EN 60898) at 230 V
6 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
6 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
10 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
10 kA
Overvoltage category
III
Pollution degree
2

Technical data - mechanical

Width in number of modular spacings
2
Built-in depth
70.5 mm
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
40 A
Equipment heat dissipation, current-dependent
7.5 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3
Features
Additional equipment possible

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.