View larger
FAZ-D40/4-NA 190843 Y7-190843 EATON ELECTRIC Miniature circuit breaker (MCB), D40, 4 poles, NA
FAZ-D40/4-NA
190843
Y7-190843
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller miniature circuit breaker FAZ-D40/4-NA (FAZ-D40/4-NA 190843 Y7-190843) is implemented in electrical distribution boards to safeguard wiring networks from the damaging effects of electrical overloads and short circuits. This automatic protective device ensures reliable circuit isolation when abnormal currents are detected.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): D
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 40 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 12.4 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
CSA (Class No. 1432-01)
UL 489
CSA (File No. 204453)
North America (UL listed, CSA certified)
IEC/EN 60947-2
UL (Category Control Number DIVQ)
UL (File No. E235139)
IEC 60947-2
Specially designed for North America, suitable as BCPD
CE marking
UL 489, CSA C22.2 No. 5
EN45545-2
IEC 61373
Delivery program
- FAZ-NA
- Miniature circuit breaker
Technical data - electrical
min. 6000 operations (UL)
Technical data - mechanical
IP20 (IEC)
IP20
UL/CSA Type: -
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 4 Nm (36 lb-in) for AWG 6
Max. 2.4 Nm
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
FAZ-NA
Miniature circuit breaker