EATON - MOELLER FAZ-D1,6/3 FAZ-D1,6/3 278883 Y7-278883 EATON ELECTRIC Miniature circuit breaker (MCB), 1, 6A, 3p, D-Char, AC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FAZ-D1,6/3 278883 Y7-278883 EATON ELECTRIC Miniature circuit breaker (MCB), 1, 6A, 3p, D-Char, AC

FAZ-D1,6/3

278883

Y7-278883

EATON - MOELLER

1 Pcs.

Miniature circuit breaker (MCB), 1, 6A, 3p, D-Char, AC FAZ-D1,6/3 Eaton Moeller series xEffect - FAZ MCB. FAZ, 3-pole, tripping characteristic: D, rated current In: 1.6 A Miniature circuit breaker (MCB), FAZ, 3-pole, tripping characteristic: D, rated current In: 1.6 A, Switchgear for industrial and advanced commercial applications

Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series xEffect - FAZ MCB
Catalog Number
278883
Model Code
FAZ-D1,6/3
EAN
4015082788834
Product Length/Depth
80 mm
Product Height
75.5 mm
Product Width
54 mm
Product Weight
0.339 kg
Compliances
UL CSA09 (with supplementary protector only)
RoHS conform
Certifications
CSA-C22.2 No. 235
CSA (Class No. 3215-30)
CSA (File No. 204453)
IEC/EN 60947-2
North America (UL recognized, CSA certified)
IEC/EN 60898
CE marking
UL 1077
UL (Category Control Number QVNU2, QVNU8)
UL (File No. E177451)
EN45545-2
IEC 61373

Product specifications

Type
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Application
  • Branch circuits, not as BCPD
  • Switchgear for industrial and advanced commercial applications
  • xEffect - Switchgear for industrial and advanced commercial applications
Amperage Rating
1.6 A
Voltage rating
240 V AC / 415 V AC
Features
Additional equipment possible
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
2
Used with
Miniature circuit breaker
FAZ
Degree of protection
IP20
UL/CSA Type: -
IP20 (IEC)
Equipment heat dissipation, current-dependent
3.8 W
Rated impulse withstand voltage (Uimp)
4 kV
Tripping characteristic
D
Voltage rating (UL CSA 13)
480 Y/277 V AC
Ambient operating temperature - max
75 °C
Ambient operating temperature - min
-25 °C
Built-in depth
70.5 mm
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Current limiting class
3
Frequency rating - max
60 Hz
Frequency rating - min
50 Hz
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Width in number of modular spacings
3
Voltage type
AC
Overvoltage category
III
Number of poles
Three-pole
Release characteristic
D
Number of poles (protected)
3
Number of poles (total)
3
Rated insulation voltage (Ui)
440 V
Rated operational current for specified heat dissipation (In)
1.6 A
Rated operational voltage (Ue) - max
400 V
Rated short-circuit breaking capacity (EN 60898) at 230 V
10 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
10 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
15 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
15 kA
Rated switching capacity (IEC/EN 60947-2)
15 kA
Static heat dissipation, non-current-dependent
0 W
Power loss
3.9 W

ETIM for 278883 Circuit breakers and fuses (EC000042)
Feature Name Feature Value
Built-in depth (EF000218) 70.5 mm
Release characteristic (EF000889) D
Number of poles (total) (EF008618) 3
Number of protected poles (EF005548) 3
Rated current (EF000227) 1.6 A
Rated voltage (EF000228) 400 V
Rated insulation voltage Ui (EF001366) 440 V
Rated impulse withstand voltage Uimp (EF011980) 4 kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (EF009556) 10 kA
Voltage type (EF000187) AC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555) 10 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (EF009557) 15 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558) 15 kA
Frequency (EF000416) 50 Hz
Power loss (EF005387) 3.9 W
Current limiting class (EF002568) 3
Flush-mounted installation (EF007517) No
Concurrently switching neutral conductor (EF005997) No
Over voltage category (EF002569) 3
Pollution degree (EF002570) 2
Additional equipment possible (EF008148) Yes
Width in number of modular spacings (EF002950) 3
Degree of protection (IP) (EF005474) IP20
Ambient temperature during operating (EF007515) -25 °C
Connectable conductor cross section multi-wired (EF007343) 1 mm²
Connectable conductor cross section solid-core (EF007337) 1 mm²
Explosion-proof (EF004663) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.