Circuit protection devices of this classification are installed in electrical panels to monitor current flow and automatically disconnect loads during overloads or short circuits. The Eaton Moeller FAZ-C8/4-RT provides multi-pole switching to secure complex branch circuits against electrical faults.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): C
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 8 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 5.2 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
CE marking
UL (Category Control Number DIVQ)
CSA (Class No. 1432-01)
IEC/EN 60947-2
UL (File No. E235139)
UL 489
Specially designed for North America, suitable as BCPD
UL 489, CSA C22.2 No. 5
CSA (File No. 204453)
CSA-C22.2 No. 5-09
North America (UL listed, CSA certified)
EN45545-2
IEC 61373
Delivery program
- FAZ-RT
- Miniature circuit breaker
Technical data - electrical
min. 6000 operations (UL)
Technical data - mechanical
IP40 (when fitted)
UL/CSA Type: -
IP20 (IEC)
UL: 4 Nm (36 lb-in) for AWG 6
Max. 2.4 Nm
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
Miniature circuit breaker
FAZ-RT
FAZ-XAA-NA110-415V AC 102036 (Shunt trip release)
FAZ-XAA-NA12-110V AC 102037 (Shunt trip release)