View larger
FAZ-C7/4-NA 190924 Y7-190924 EATON ELECTRIC Miniature circuit breaker (MCB), C7, 4 poles, NA
FAZ-C7/4-NA
190924
Y7-190924
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller FAZ-C7/4-NA 190924 Y7-190924 EATON ELECTRIC Miniature circuit breaker (MCB), C7, 4 poles, NA offers four-pole overcurrent protection designed to meet North American application standards. Miniature circuit breakers are critical safety elements in industrial control panels, safeguarding sensitive machinery and internal wiring from overload and short-circuit risks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): C
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 7 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 5.6 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
North America (UL listed, CSA certified)
IEC 60947-2
CSA (Class No. 1432-01)
CSA (File No. 204453)
CSA-C22.2 No. 5-09
UL (File No. E235139)
CE marking
IEC/EN 60947-2
UL (Category Control Number DIVQ)
UL 489, CSA C22.2 No. 5
Specially designed for North America, suitable as BCPD
EN45545-2
IEC 61373
Delivery program
- FAZ-NA
- Miniature circuit breaker
Technical data - electrical
min. 1500 operations
Technical data - mechanical
IP20 (IEC)
UL/CSA Type: -
IP20
UL: 4 Nm (36 lb-in) for AWG 6
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Max. 2.4 Nm
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
Miniature circuit breaker
FAZ-NA