Request QuoteProduct Overview
An FAZ-C0,5/4-RT 190863 Y7-190863 EATON ELECTRIC FAZ-C0,5/4-RT functions as a multi-pole circuit breaker engineered for reliable overcurrent protection in complex control panels. These modular units are standard elements in electrical enclosures, providing automated disconnection to protect machinery and wiring from overloads. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): C
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 0.5 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
North America (UL listed, CSA certified)
CSA (Class No. 1432-01)
UL 489, CSA C22.2 No. 5
UL 489
IEC 60947-2
CSA-C22.2 No. 5-09
IEC/EN 60947-2
CE marking
UL (File No. E235139)
UL (Category Control Number DIVQ)
Specially designed for North America, suitable as BCPD
EN45545-2
IEC 61373
Delivery program
- FAZ-RT
- Miniature circuit breaker
Technical data - electrical
min. 1500 operations
Technical data - mechanical
IP40 (when fitted)
UL/CSA Type: -
IP20 (IEC)
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 4 Nm (36 lb-in) for AWG 6
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
FAZ-RT