View larger
FAZ-B63/2-RT 190800 Y7-190800 EATON ELECTRIC FAZ-B63/2-RT
FAZ-B63/2-RT
190800
Y7-190800
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller FAZ-B63/2-RT circuit breaker protects high-current electrical installations against thermal overloads and short circuits by safely breaking fault currents. It is commonly deployed in commercial and industrial electrical panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): B
- Number of poles (total) (EF008618): 2
- Number of protected poles (EF005548): 2
- Rated current (EF000227): 63 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 11 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
CSA (Class No. 1432-01)
UL (File No. E235139)
IEC/EN 60947-2
UL (Category Control Number DIVQ)
UL 489, CSA C22.2 No. 5
North America (UL listed, CSA certified)
Specially designed for North America, suitable as BCPD
UL 489
CSA (File No. 204453)
CE marking
CSA-C22.2 No. 5-09
EN45545-2
IEC 61373
Delivery program
- FAZ-RT
- Miniature circuit breaker
Technical data - electrical
min. 6000 operations (UL)
Technical data - mechanical
UL/CSA Type: -
IP40 (when fitted)
IP20 (IEC)
UL: 4 Nm (36 lb-in) for AWG 6
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
Max. 2.4 Nm
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
FAZ-RT
Miniature circuit breaker