View larger
FAZ-B6/4-NA 190905 Y7-190905 EATON ELECTRIC Miniature circuit breaker (MCB), B6, 4 poles, NA
FAZ-B6/4-NA
190905
Y7-190905
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The FAZ-B6/4-NA 190905 Y7-190905 EATON ELECTRIC Miniature circuit breaker (MCB), B6, 4 poles, NA is a four-pole protective device engineered to secure multi-phase electrical distribution networks against thermal overloads and short circuits. Miniature circuit breakers are essential components in industrial control panels, ensuring rapid power disconnection during fault conditions. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): B
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 6 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 7.2 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
IEC/EN 60947-2
IEC 60947-2
CSA (Class No. 1432-01)
Specially designed for North America, suitable as BCPD
North America (UL listed, CSA certified)
CSA-C22.2 No. 5-09
CE marking
UL (Category Control Number DIVQ)
UL 489, CSA C22.2 No. 5
CSA (File No. 204453)
UL (File No. E235139)
EN45545-2
IEC 61373
Delivery program
- FAZ-NA
- Miniature circuit breaker
Technical data - electrical
min. 6000 operations (UL)
Technical data - mechanical
IP40 (when fitted)
IP20 (IEC)
UL/CSA Type: -
UL: 4 Nm (36 lb-in) for AWG 6
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Max. 2.4 Nm
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
Miniature circuit breaker
FAZ-NA
FAZ-XAA-NA110-415V AC 102036 (Shunt trip release)
FAZ-XAA-NA12-110V AC 102037 (Shunt trip release)