EATON - MOELLER FAZ-B5/1-RT FAZ-B5/1-RT 132736 Y7-132736 EATON ELECTRIC Int. circuit breaker FAZ-RT, 5A, 1P, curve B View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FAZ-B5/1-RT 132736 Y7-132736 EATON ELECTRIC Int. circuit breaker FAZ-RT, 5A, 1P, curve B

FAZ-B5/1-RT

132736

Y7-132736

EATON - MOELLER

1 Pcs.

Int. circuit breaker FAZ-RT, 5A, 1P, curve B FAZ-B5/1-RT Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. Miniature circuit breaker (MCB), 5 A, 1p, characteristic: B, ring tongue Miniature circuit breaker (MCB), FAZ-RT, 1-pole, tripping characteristic: B, rated current In: 5 A, Switchgear for industrial and advanced commercial applications

Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Eaton Moeller FAZ-B5/1-RT 132736 Y7-132736 EATON ELECTRIC Int. circuit breaker FAZ-RT, 5A, 1P, curve B is a protective electrical switching device used in industrial and commercial distribution boards to safeguard wiring against overcurrents and short circuits. Such miniature circuit breakers interrupt fault currents automatically to prevent equipment damage and electrical hazards.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Built-in depth (EF000218): 70.5 mm
  • Release characteristic (EF000889): B
  • Number of poles (total) (EF008618): 1
  • Number of protected poles (EF005548): 1
  • Rated current (EF000227): 5 A
  • Rated voltage (EF000228): 240 V
  • Rated insulation voltage Ui (EF001366): 440 V
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Voltage type (EF000187): AC
  • Frequency (EF000416): 50 Hz
  • Power loss (EF005387): 1.9 W
  • Current limiting class (EF002568): 3
  • Flush-mounted installation (EF007517): No
  • Concurrently switching neutral conductor (EF005997): No
  • Over voltage category (EF002569): 3
  • Pollution degree (EF002570): 2

More info

▲

General specifications

Product Name
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
Catalog Number
132736
Model Code
FAZ-B5/1-RT
EAN
4015081296859
Product Length/Depth
105 mm
Product Height
75.5 mm
Product Width
17.7 mm
Product Weight
0.123 kg
Compliances
RoHS conform
Certifications
IEC 60947-2
CSA (File No. 204453)
UL (Category Control Number DIVQ)
Specially designed for North America, suitable as BCPD
CSA-C22.2 No. 5-09
CSA (Class No. 1432-01)
IEC/EN 60947-2
UL 489
UL 489, CSA C22.2 No. 5
North America (UL listed, CSA certified)
CE marking
UL (File No. E235139)
EN45545-2
IEC 61373

Delivery program

Application
Number of poles
Single-pole
Number of poles (total)
1
Number of poles (protected)
1
Tripping characteristic
B
Release characteristic
B
Amperage Rating
5 A
Type
  • FAZ-RT
  • Miniature circuit breaker

Technical data - electrical

Voltage type
AC
Voltage rating
277 V AC / 480 V AC
Voltage rating at DC
60 V DC
Voltage rating (IEC/EN 60947-2)
254 V
Voltage rating (UL)
277 V
Rated operational voltage (Ue) - max
240 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2)
15 kA
Breaking capacity
10 kA (UL489)
Rated short-circuit breaking capacity (EN 60898) at 230 V
0 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
15 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
15 kA
Selectivity class
3
Overvoltage category
III
Pollution degree
2
Lifespan, electrical
20000 operations
Direction of incoming supply
As required

Technical data - mechanical

Frame
45 mm
Enclosure width
105 mm
Width in number of modular spacings
1
Built-in depth
70.5 mm
Mounting width per pole
17.7 mm
Mounting width
17.7 mm
Mounting Method
Top-hat rail IEC/EN 60715
Mounting position
As required
Degree of protection
IP20 (IEC)
IP20
IP40 (when fitted)
UL/CSA Type: -
Terminals (top and bottom)
Twin-purpose terminals
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Tightening torque
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Max. 2.4 Nm
UL: 4 Nm (36 lb-in) for AWG 6

Design verification as per IEC/EN - technical data

Rated operational current for specified heat dissipation (In)
5 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
1.8 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Additional information

Current limiting class
3
Features
Additional equipment possible
Functions
Current limiting circuit breaker
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used with
FAZ-RT
Miniature circuit breaker

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.