EATON - MOELLER FAZ-B16/4 FAZ-B16/4 279035 Y7-279035 EATON ELECTRIC Miniature circuit breaker (MCB), 16A, 4p, B-Char, AC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FAZ-B16/4 279035 Y7-279035 EATON ELECTRIC Miniature circuit breaker (MCB), 16A, 4p, B-Char, AC

FAZ-B16/4

279035

Y7-279035

EATON - MOELLER

1 Pcs.

Miniature circuit breaker (MCB), 16A, 4p, B-Char, AC FAZ-B16/4 Eaton Moeller series xEffect - FAZ MCB. FAZ, 4 pole, tripping characteristic: B, rated current In: 16 A Miniature circuit breaker (MCB), FAZ, 4 pole, tripping characteristic: B, rated current In: 16 A, Switchgear for industrial and advanced commercial applications

Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A miniature circuit breaker is designed to protect low-voltage electrical circuits from damage caused by excess current from an overload or short circuit. These switching devices are fundamental components in electrical distribution boards and industrial control enclosures.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Built-in depth (EF000218): 70.5 mm
  • Release characteristic (EF000889): B
  • Number of poles (total) (EF008618): 4
  • Number of protected poles (EF005548): 4
  • Rated current (EF000227): 16 A
  • Rated voltage (EF000228): 400 V
  • Rated insulation voltage Ui (EF001366): 440 V
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Voltage type (EF000187): AC
  • Frequency (EF000416): 50 Hz
  • Power loss (EF005387): 7.5 W
  • Current limiting class (EF002568): 3
  • Flush-mounted installation (EF007517): No
  • Concurrently switching neutral conductor (EF005997): Yes
  • Over voltage category (EF002569): 3
  • Pollution degree (EF002570): 2

More info

▲

General specifications

Product Name
Eaton Moeller series xEffect - FAZ MCB
Catalog Number
279035
Model Code
FAZ-B16/4
EAN
4015082790356
Product Length/Depth
80 mm
Product Height
75.5 mm
Product Width
72 mm
Product Weight
0.445 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947-2
IEC/EN 60898
EN45545-2
IEC 61373

Delivery Programme

Application
Number of poles
Four-pole
Number of poles (total)
4
Number of poles (protected)
4
Tripping characteristic
B
Release characteristic
B
Amperage Rating
16 A
Type
  • FAZ
  • Miniature circuit breaker

Technical data - electrical

Voltage type
AC
Voltage rating
240 V AC / 415 V AC
Voltage rating at DC
60 V DC (per pole)
Voltage rating (IEC/EN 60898-1)
415 VAC
Voltage rating (UL)
480Y/277 V
Rated operational voltage (Ue) - max
400 V
Operational voltage (IEC/EN 60947-2) - max
440 VAC
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2) at max voltage rating
10 kA
Rated switching capacity (IEC/EN 60947-2)
15 kA
Rated switching capacity (IEC/EN 60898-1)
10 kA
Operational switching capacity
7.5 kA
Breaking capacity
10 kA (UL1077)
Rated service short-circuit breaking capacity (IEC/EN 60898-1)
7.5 kA
Rated service short-circuit breaking capacity (IEC/EN 60947-2)
7.5 kA
Rated short-circuit breaking capacity (EN 60898) at 230 V
10 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
10 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
15 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
15 kA
Admissible back-up fuse - max
125 A gL/gG
Selectivity class
3
Overvoltage category
III
Pollution degree
2
Lifespan, electrical
10000 operations
Direction of incoming supply
As required

Technical data - mechanical

Frame
45 mm
Enclosure width
80 mm
Width in number of modular spacings
4
Built-in depth
70.5 mm
Mounting width per pole
17.5 mm
Mounting width
17.5 mm
Mounting Method
Top-hat rail IEC/EN 60715
Mounting position
As required
Degree of protection
IP40 (when fitted)
IP20
Terminals (top and bottom)
Twin-purpose terminals
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Terminal capacity of screw terminals for main cable
10 mm² (2x)
Terminal capacity (control cable)
25 mm² (1x)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Busbar material thickness
0.8 mm - 2 mm

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
16 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
8.8 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Additional information

Current limiting class
3
Features
Concurrently switching N-neutral
Additional equipment possible
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used with
Miniature circuit breaker
FAZ

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.