Request QuoteProduct Overview
Engineered to safeguard electrical networks from overcurrents, the FAZ-B13/4-RT 190854 Y7-190854 EATON ELECTRIC FAZ-B13/4-RT acts as an automatic switch that trips during fault conditions. Such components are frequently integrated into electrical distribution boards to protect sensitive machinery and branch circuits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 60 mm
- Release characteristic (EF000889): B
- Number of poles (total) (EF008618): 4
- Number of protected poles (EF005548): 4
- Rated current (EF000227): 13 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Power loss (EF005387): 10 W
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): Yes
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
More info
▲General specifications
UL (Category Control Number DIVQ)
North America (UL listed, CSA certified)
IEC 60947-2
CE marking
CSA (Class No. 1432-01)
UL 489, CSA C22.2 No. 5
CSA-C22.2 No. 5-09
UL 489
IEC/EN 60947-2
Specially designed for North America, suitable as BCPD
UL (File No. E235139)
EN45545-2
IEC 61373
Delivery program
- FAZ-RT
- Miniature circuit breaker
Technical data - electrical
min. 6000 operations (UL)
Technical data - mechanical
IP20
IP20 (IEC)
IP40 (when fitted)
Max. 2.4 Nm
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Design verification as per IEC/EN - technical data
Design verification as per IEC/EN 61439
Additional information
- Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
- Tripping signal contact for subsequent installation Z-NHK 248434
Miniature circuit breaker
FAZ-RT