EATON - MOELLER BK25/3-PKZ0-E BK25/3-PKZ0-E 262518 Y7-262518 EATON ELECTRIC Extension terminal, 3p, 25mm² View larger
Images are for illustrative purposes only. Please refer to data sheet for details

BK25/3-PKZ0-E 262518 Y7-262518 EATON ELECTRIC Extension terminal, 3p, 25mm²

BK25/3-PKZ0-E

262518

Y7-262518

EATON - MOELLER

1 Pcs.

Extension terminal, 3p, 25mm² BK25/3-PKZ0-E Eaton Moeller® series PKZ Extension terminal, 3p, 25mm² BK25/3-PKZ0-E Connection clamp, Product range: Accessories, For use with: PKZM0, PKE12, PKE32

Automation > Busbar terminal
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Engineered as an Eaton Moeller BK25/3-PKZ0-E extension terminal, this 3-pole accessory simplifies wiring expansion for motor-protective circuit breakers. Panel builders use multi-pole terminals to streamline incoming power distribution across grouped switching devices.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Busbar thickness (EF007220): 0 mm
  • Busbar width (EF007219): 0 mm
  • Width clamp (EF007092): 45 mm
  • Max. conductor cross section (EF004969): 25 mm²
  • Max. rated operation current Ie (EF007356): 63 A
  • Suitable for round conductor connection (EF007258): Yes
  • Suitable for sector conductor connection (EF007260): No
  • Suitable for strip conductor connection (EF007242): No

More info

General specifications

Product Name
Eaton Moeller® series PKZ Connection clamp
Catalog Number
262518
Model Code
BK25/3-PKZ0-E
EAN
4015082625184
Product Length/Depth
34 mm
Product Height
45 mm
Product Width
45 mm
Product Weight
0.047 kg
Certifications
CSA
UL File No.: E36332
CSA Class No.: 3211-06
UL
UL 508
CSA-C22.2 No. 14
IEC/EN 60947-4-1
CE
CSA File No.: 98494
UL Category Control No.: NLRV

General

Overvoltage category
III
Pollution degree
3
Product category
Accessories
Suitable for
Round conductor connection
PKZM0/PKE, line terminal required for Type E/F applications, (UL/CSA)
Other

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Electrical rating

Rated operational current (Ie) - max
63 A

Design verification

Equipment heat dissipation, current-dependent Pvid
5.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.8 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.