View larger
EWK-08051 174653 EATON ELECTRIC EWK-08051 EWK wall-mount enclosure with standard mounting units, 108 SU, IP4..
EWK-08051
174653
EATON - MOELLER
1 Pcs.
Automation > Enclosure/switchgear cabinet (empty)
Compact Distribution Boxes
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The EWK-08051 174653 Eaton Electric EWK-08051 EWK wall-mount enclosure with standard mounting units, 108 SU, IP4.. serves as a specialized housing unit for DIN rail-mounted modular devices and low-voltage distribution components. Installers utilize wall-mount enclosures to organize circuit protection and control apparatus in commercial buildings and industrial facilities. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rows: Count
- PE and N terminals: Number x cross-sectional area
- Rated operational voltage: Ue
- Rated frequency: f
- Individual enclosure for wall mounting: P V
- Starting enclosure for wall mounting: P V
- Middle enclosure for wall mounting: P V
- Individual enclosure for wall mounting: P V
- Starting enclosure for wall mounting: P V
- Middle enclosure for wall mounting: P V
- IL014004Z EWK enclosures for DIN rail-mounted devices: >>
- Width (EF000008): 800 mm
- Height (EF000040): 500 mm
- Depth (EF000049): 160 mm
- Material (EF002169): Steel
- Colour (EF000007): White
More info
▲Basic function | Basic device | ||
Product function | Installation distribution boards | ||
Product range | EWK DBO | ||
Design | Surface mounted | ||
Installation site | Indoor | ||
Type of installation | Surface mounting | ||
Door/Flap | White | ||
Degree of Protection | IP43 | ||
Colour | White | ||
Module rack | Rail-frame | ||
Shroud for protection against accidental contact | Plastic | ||
Rows | Count | 3 | |
Module units per row | 36 | ||
Description | IP43 Protection Class II Steel sheet enclosure white (RAL 9016) | ||
Cable entries | Cable entries on top and bottom, back plate | ||
PE and N terminals design | Plug-in terminals | ||
PE and N terminals | Number x cross-sectional area | mm2 | PE: 3 x 6 x (1.5 - 16) N: 3 x 21 x (0.75 - 4) |
Equipment supplied | Enclosure Installation panel for modular installation devices Neutral-/protective conductor terminal Locking screws can be sealed Two-component membrane gland plate insert |
| General | |||
Standards | EN 61439-3 | ||
RoHS (in accordance with Directive 2002/95/EC of the European Parliament and Council) | conform | ||
Ambient temperature | °C | -5 - +40 | |
Degree of Protection | IP43 | ||
Protection class | II (totally insulated) | ||
Rated operational voltage | Ue | V AC | 400 |
Rated frequency | f | Hz | 50 |
| Material characteristics | |||
Material | Sheet steel, powder-coated Polystyren (plastic) | ||
Colour | white (RAL 9016) | ||
| Material properties | |||
Mechanical | |||
Impact resistance | IK09 | ||
Technical data for design verification | |||
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 58 |
Starting enclosure for wall mounting | PV | CO | 57 |
Middle enclosure for wall mounting | PV | CO | 55 |
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 117 |
Starting enclosure for wall mounting | PV | CO | 113 |
Middle enclosure for wall mounting | PV | CO | 110 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | 750 °C; meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Not relevant to indoor installations. | ||
10.2.5 Lifting | Does not apply to enclosures without lifting aids. | ||
10.2.6 Mechanical impact | IK09 | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | IP43 | ||
10.4 Clearances and creepage distances | Is the panel builder's responsibility. | ||
10.5 Protection against electric shock | Protection class 2, therefore not applicable. | ||
10.6 Incorporation of switching devices and components | Is the panel builder's responsibility. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Ui= 400 V AC | ||
10.9.3 Impulse withstand voltage | 3 kV | ||
10.9.4 Testing of enclosures made of insulating material | Does not apply to metal enclosures. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. | ||
10.13 Mechanical function | Meets the product standard's requirements. |
| Cabinet enclosures (EG000011) / Enclosure/switchgear cabinet (empty) (EC000261) | |||
| Electric engineering, automation, process control engineering / Electrical cabinet, housing, rack / Electrical cabinet (empty) / Electrical cabinet ([email protected] [AGZ056013]) | |||
Width | mm | 800 | |
Height | mm | 500 | |
Depth | mm | 160 | |
Material | Steel | ||
Type of surface | With powder coating | ||
Colour | White | ||
RAL-number | 9016 | ||
With mounting plate | No | ||
Mounting plate depth-adjustable | No | ||
Number of locks | 1 | ||
Floor installation possible | No | ||
Wall fastening possible | Yes | ||
Wall build in | Yes | ||
Pole fastening | No | ||
Tackable | Yes | ||
Number of doors | 2 | ||
Suitable for metrical mounting | Yes | ||
Suitable for outdoor set-up | No | ||
Pitched roof | No | ||
EMC-version | Yes | ||
Impact strength | IK09 | ||
Degree of protection (IP) | IP43 | ||
With glazed door | No | ||
With ventilation door | No | ||
With backside door | No | ||