EU5C-SWD-PROFINET 170124 Y7-170124 EATON ELECTRIC Gateway SWDT, PROFINET Up to 99 modules
EU5C-SWD-PROFINET
170124
Y7-170124
EATON - MOELLER
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
Smartwire Darwin
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An EU5C-SWD-PROFINET 170124 Y7-170124 EATON ELECTRIC Gateway SWDT, PROFINET Up to 99 modules functions as a network communication bridge that links decentralized field devices to upper-level automation systems. Gateways like this are widely utilized in factory automation to facilitate seamless data exchange between proprietary fieldbuses and standard industrial Ethernet infrastructures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 0 V
- Supply voltage AC 60 Hz (EF007533): 0 V
- Supply voltage DC (EF007534): 20.4 V
- Voltage type (supply voltage) (EF002991): DC
- Number of HW-interfaces CAN (EF017563): 0
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 2
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 1
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- Supporting protocol for EtherCAT (EF017564): No
More info
▲General specifications
UL Category Control No.: NRQA
UL File No.: E221530
UL
IEC/EN 61131-2
UL report applies to both US and Canada
Features & Functions
Overload proof
General
Rail mounting possible
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Wall mounting/direct mounting
0.25 - 1.5 mm², flexible with ferrule
24 - 16 AWG, solid or stranded
Ambient conditions, mechanical
Climatic environmental conditions
Electro magnetic compatibility
1 kV
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
Electrical rating
24 V DC (UAUX, -15 %/+20 %)
Typically UAUX -0.2 V (for 24 V DC slaves)
No, external fuse FAZ Z3, Supply voltage UAux
Communication
Used to connect the SmartWire-DT communication system to industrial field bus systems. Powers SmartWire-DT modules and switchgear
SmartWire-DT blade terminal SWD4-8MF2
A connection to PROFINET as a PROFINET I/O device can be established using the integrated 100 Mbit/s Ethernet switch and a slave configuration.
Push in terminals, Supply voltage
2 x RJ45 (2-channel switch), Field bus interface
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
800 Byte, Fieldbus interface, Input data, max.
100 MBit/s, Fieldbus interface
Status display fieldbus interface for APL, SF, BF, LINK, RX/TX with Multi colour LED
Status indication of Supply voltage: LED
Status indication of SmartWire-DT network: Configurable green or red LED
PROFINET
SmartWire-DT master, SmartWire-DT network
Safety
Between UPow and 15 V SmartWire-DT supply voltage: no
Yes, for supply voltage (Siemens MPI optional)