View larger
EMT62-DB 171890 Y7-171890 EATON ELECTRIC Thermistor overload relays for machine protection, 2 N/O, 24 240 V ..
EMT62-DB
171890
Y7-171890
EATON - MOELLER
1 Pcs.
Automation > Temperature monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Eaton Moeller EMT62-DB thermistor overload relay is a protective electrical switching component designed to safeguard industrial motors against overheating. It monitors winding temperatures via embedded sensors and interrupts the control circuit if thermal limits are exceeded, preventing premature motor failure in demanding applications.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Number of measuring circuits (EF003425): 2
- Error registration possible (EF003423): No
- External reset possible (EF003426): Yes
- Temperature measuring range (EF009788): 0 °C
- Resistance measuring range (EF011955): 750 Ohm
- Connection type auxiliary circuit (EF006820): Screw connection
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 2
- Number of contacts as change-over contact (EF008257): 0
- Voltage type (operating voltage) (EF005294): AC/DC
More info
▲General specifications
IEC/EN 60947-8
CSA
CSA Class No.: 3211-03
IEC/EN 61000-4-2
EN 55011
UL Category Control No.: NKCR
CSA File No.: 12528
IEC/EN 60947
VDE 0660
IEC/EN 61000-4-3
UL
UL File No.: E29184
CSA-C22.2 No. 14
UL 508
Features & Functions
Test function via separate button
External reset possible
Manual reset
Notifications of mains and faults via LED display
General
250 V AC, Between the contacts and power supply, According to EN 61140
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro magnetic compatibility
1 kV, Signal cable
According to IEC/EN 61000-4-4
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
4 kV, asymmetrical, power pulses (Surge), EMC
2 kV, symmetrical, power pulses (Surge), EMC
Terminal capacities
1 x (0.5 - 2.5) mm², flexible with ferrule
1 x (0.5 - 2.5) mm², solid
20 - 14 AWG, solid or stranded
2 x (0.5 - 1.5) mm², flexible with ferrule
2, Terminal screw, Pozidriv screwdriver
Electrical rating
3.5 VA at AC
3 A at AC-15, 220 V 230 V 240 V (NO)
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 400 V (NC)
3 A at AC-14, 380 V 400 V 415 V (NO)