Request QuoteProduct Overview
An Eaton Moeller EMS2-ROS-T-9-24VDC electronic reversing starter provides solid-state motor control, reversing, and electronic overload protection for industrial drives. Electronic hybrid starters offer extended operational lifespans and compact footprints in control enclosures. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Reversing starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 1.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 9 A
- Rated operation current at AC-3, 400 V (EF009602): 7 A
- Overload release current setting (EF002336): 1.5 A
- Power consumption (EF000346): 12 W
- Ambient temperature, upper operating limit (EF009603): 70 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
UL508
EN ISO 13849
IEC 61508
UL File No.: E338590
UL Category Control No.: NLDX, NLDX7
PTB 19 ATEX 3000
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE marking
UL listed
Certified by UL for use in Canada
UL report applies to both US and Canada
Features & Functions
DOL starting
Motor protection
Reversing start
General
NEMA Other
Rail mounting possible
Vertical
0.2 - 2.5 mm², Main cables
0.14 - 2.5 mm², Control circuit cables
24 - 14, Main cables
24 - 14, Main cables, Push-in terminals
Climatic environmental conditions
Electro magnetic compatibility
Class A (EN 61000-6-3, emitted interference, radiated)
Electrical rating
500 V AC
-3 - 9.6 V DC, Switching level "Low", Actuating circuit (ON, L, R)
< 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R)
Contacts
Safety
ATEX dust-ex-protection, II (2) D [Ex t] [Ex p]
3 (safe switch off), Category
60 (safe switch off) / 70 (motor protection) years; MTTFD
Λsd [FIT]: 0
Λsu [FIT]: 1072 (Safe switch off) / 969 (Motor protection)
99 % (safe switch off) / 98 % (motor protection), DC
Λdd [FIT]: 580 (Safe switch off) / 601 (Motor protection)
SIL 3 (Safe switch off) / SIL 2 (Motor protection)
Opening delay [ms]: 200 (safe switch off) / Class 10A (motor protection)
99 %, SFF
PFHd [FIT]: 2.3 (Safe switch off)