Incorporating emergency stop capabilities and wide operating temperature tolerances up to 70 °C, the Eaton Moeller EMS2-DOS-Z-9-24VDC 197166 Y7-197166 EATON ELECTRIC Starter electronic direct Start 9 A 24 V DC Emergency Sto.. functions as an electronic direct motor starter. Electronic starters offer durable semiconductor switching and precise overload protection for industrial drives. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 1.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 9 A
- Rated operation current at AC-3, 400 V (EF009602): 7 A
- Overload release current setting (EF002336): 1.5 A
- Power consumption (EF000346): 12 W
- Ambient temperature, upper operating limit (EF009603): 70 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
IEC 61508
EN ISO 13849
UL508
UL File No.: E338590
UL Category Control No.: NLDX, NLDX7
PTB 19 ATEX 3000
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE marking
UL listed
Certified by UL for use in Canada
UL report applies to both US and Canada
Features & Functions
Motor protection
Controlled stop
DOL starting
General
NEMA Other
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Motor feeder at bottom
0.14 - 2.5 mm², Control circuit cables
0.2 - 2.5 mm², Main cables, Push-in terminals
24 - 14, Main cables
Climatic environmental conditions
Electro magnetic compatibility
EN 55011
Electrical rating
42 - 550 V
19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R)
< 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R)
Contacts
Safety
ATEX dust-ex-protection, II (2) G [Ex e] [Ex d] [Ex px]
3 (safe switch off), Category
60 (safe switch off) / 70 (motor protection) years; MTTFD
99 % (safe switch off) / 98 % (motor protection), DC
SIL 3 (Safe switch off) / SIL 2 (Motor protection)
Opening delay [ms]: 200 (safe switch off) / Class 10A (motor protection)
PFHd [FIT]: 2.3 (Safe switch off)
Λsd [FIT]: 0
Λsu [FIT]: 1072 (Safe switch off) / 969 (Motor protection)
Λdu [FIT]: 2.3 (Safe switch off) / 11 (Motor protection)