View larger
EMS2-DOS-T-9-24VDC 192397 Y7-192397 EATON ELECTRIC Starter electronic direct Start 9 A 24 V DC Emergency Sto..
EMS2-DOS-T-9-24VDC
192397
Y7-192397
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A starter electronic direct start 9 A 24 V DC emergency sto.. manufactured by Eaton Moeller, part number EMS2-DOS-T-9-24VDC, delivers solid-state direct-on-line motor starting with integrated safety stop functions. Electronic direct starters offer wear-free switching for frequent operation cycles in modern industrial processing and material handling equipment. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 1.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 9 A
- Rated operation current at AC-3, 400 V (EF009602): 7 A
- Overload release current setting (EF002336): 1.5 A
- Power consumption (EF000346): 12 W
- Ambient temperature, upper operating limit (EF009603): 70 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
IEC 61508
IEC/EN 60947-4-2
EN ISO 13849
UL File No.: E338590
UL Category Control No.: NLDX, NLDX7
PTB 19 ATEX 3000
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE marking
UL listed
Certified by UL for use in Canada
UL report applies to both US and Canada
Features & Functions
Temperature compensated overload protection
Motor protection
DOL starting
General
NEMA Other
Rail mounting possible
Vertical
0.2 - 2.5 mm², Main cables
0.14 - 2.5 mm², Control circuit cables
24 - 14, Main cables
24 - 14, Main cables, Push-in terminals
Climatic environmental conditions
Electro magnetic compatibility
EN 55011
Electrical rating
500 V AC
-3 - 9.6 V DC, Switching level "Low", Actuating circuit (ON, L, R)
19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R)
Contacts
Safety
ATEX dust-ex-protection, II (2) G [Ex e] [Ex d] [Ex px]
3 (safe switch off), Category
60 (safe switch off) / 70 (motor protection) years; MTTFD
Λdu [FIT]: 2.3 (Safe switch off) / 11 (Motor protection)
Λsd [FIT]: 0
Λsu [FIT]: 1072 (Safe switch off) / 969 (Motor protection)
Opening delay [ms]: 200 (safe switch off) / Class 10A (motor protection)
PFHd [FIT]: 2.3 (Safe switch off)
SIL 3 (Safe switch off) / SIL 2 (Motor protection)
Λdd [FIT]: 580 (Safe switch off) / 601 (Motor protection)
99 %, SFF