Request QuoteProduct Overview
Eaton Electric EMS2-DOS-T-3-SWD functions as a Starter electronic direct Start 2.4 A With SmartWire-DT Eme, providing efficient motor control combined with advanced fieldbus communication. Solid-state starters with network integration capabilities allow seamless diagnostic data exchange and streamlined panel wiring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0.55 kW
- Rated operation power at AC-3, 400 V (EF001364): 1.1 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 3 A
- Rated operation current at AC-3, 400 V (EF009602): 3 A
- Overload release current setting (EF002336): 0.18 A
- Power consumption (EF000346): 2.5 W
- Ambient temperature, upper operating limit (EF009603): 55 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
IEC 61508
IEC/EN 60947-4-2
UL508
UL File No.: E338590
UL Category Control No.: NLDX, NLDX7
PTB 19 ATEX 3000
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE marking
UL listed
Certified by UL for use in Canada
UL report applies to both US and Canada
Features & Functions
DOL starting
For connecting to SmartWire-DT for expanded diagnostics
Temperature compensated overload protection
Motor protection
Automatic reset
Display of Device Type
Display of Enable signal
Manual reset
Display of Motor current in %
Display of Operating direction feedback
Operating the motor starter
Display of Operational readiness
Display of Overload prewarning
Display of Set short-circuit release value
Display of Thermal motor image in %
Display of Trip indications (overload, phase failure, etc.)
General
NEMA Other
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Motor feeder at bottom
Climatic environmental conditions
Electro magnetic compatibility
Class A (EN 61000-6-3, emitted interference, radiated)
Electrical rating
500 V AC
19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R)
< 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R)
Contacts
Safety
ATEX dust-ex-protection, II (2) D [Ex t] [Ex p]
PL e, Performance level
60 (safe switch off) / 82 (motor protection) years; MTTFD
99 % (safe switch off) / 98 % (motor protection), DC