An Eaton Moeller EMS-ROS-T-2,4-SWD starter inversor is an electronic reversing motor starter built to handle bidirectional motor operations with integrated fieldbus communication capabilities. These compact electronic units are widely used in modern machine building to reduce wiring complexity and provide fast response times for automated drives. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Reversing starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0.37 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0.736 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 2.4 A
- Rated operation current at AC-3, 400 V (EF009602): 2.4 A
- Overload release current setting (EF002336): 0.18 A
- Ambient temperature, upper operating limit (EF009603): 60 °C
- Temperature compensated overload protection (EF009604): Yes
- Release class (EF006668): CLASS 10
More info
▲Delivery program
Reversing start
Motor protection
Circuit design: safety output stage with bypass, three-phase disconnect.
Controlled stop via additional enable signal terminal up to SIL3/Ple.
Operating direction feedback
Enable signal
Motor current in %
Motor current in A
Thermal motor image in %
Overload prewarning
Trip indications (overload, phase failure, etc.)
Set short-circuit release value
Device Type
Manual reset
Automatic reset
Technical data
1 x AWG20 - 14 mm2
1 x AWG24 - 14 mm2
2 x AWG24 - 16 mm2
20 (automatic restart) min.
If ≧ 67, pick-up time of 1.8 s %
If ≧ 67, pick-up time of 1.8 s %
50 kA, 500 V AC: fuse 30 A CCMR
50 kA, 415 V AC: PKM0-4
15 kA, 415 V AC: PKM0-6,3
2.5 kA, 400 V AC: FAZ-B16/3
1.4 - 2 GHz: 10
2.0 - 2.7 GHz: 3 V/m
EN 61000-6-3, Class A (emitted interference, radiated)
IEC/EN 61000-4-4, level 3 kV
2 kV (asymmetrical)
according to IEC/EN 61000-4-5
motor protection
λsu [FIT]: 1321 (Sicheres Abschalten) / 1061 (Motorschutz)
λdd [FIT]: 685 (Sicheres Abschalten) / 577 (Motorschutz)
λdu [FIT]: 0,1 (Sicheres Abschalten) / 18 (Motorschutz)
SFF [%]: 99 (Sicheres Abschalten) / 98 (Motorschutz)
DC [%]: 99 (Sicheres Abschalten) / 96 (Motorschutz)
motor protection